Large Volume Power Burner: Gas, Oil & Dual Fuel Commercial Water Heaters
SUGGESTED SPECIFICATIONS
TITANTM LV POWER GAS (MODELS TPG)
Water heater(s) shall be Model___________________as manufactured by State Water Heaters or an approved equal. Water heater(s) shall be of
and include a powered gas burner with electronic flame safeguard, intermittent ignition, main and pilot automatic gas valves, redundant solenoid gas valve, gas pressure regulator, diaphragm air switch for proof of blower operation, and flame inspection port. Maximum supply gas pressure to heater 13˝ W.C. Heater(s) shall have an input rating of ____________ and a recovery rating of ________ GPH at a temperature rise of 100°F with a minimum actual storage capacity of ________. Heater(s) shall
be equipped with _______ NPT water inlet and outlet openings, (2) 3˝ handhole cleanouts, shall have an ASME working pressure of 160 psi, and stamped National
Board, and listed by Underwriters Laboratories. Controls shall include: high temperature limit control (manual reset), upper and lower thermostats, combination temperature and pressure gauge, low water cutoff, ASME rated temperature relief valve, drain valve and draft regulator. Control compartment door shall be hinged for easy access. The heater(s) shall be equipped with multiple anodes for cathodic protection. The heater(s) shall be insulated with
SUGGESTED SPECIFICATIONS
TITANTM LV POWER LOW NOX (MODELS TPX)
Water heater(s) shall be Model___________________as manufactured by State Water Heaters or an approved equal. Water heater(s) shall be of
and include a powered gas burner with electronic flame safeguard, intermittent ignition, main and pilot automatic gas valves, redundant solenoid gas valve, gas pressure regulator, diaphragm air switch for proof of blower operation, and flame inspection port. Maximum supply gas pressure to heater 13˝ W.C. Heater(s) shall have an input rating of ____________ and a recovery rating of ________ GPH at a temperature rise of 100°F with a minimum actual storage capacity of ________. Heater(s) shall
be equipped with _______ NPT water inlet and outlet openings, (2) 3˝ handhole cleanouts, shall have an ASME working pressure of 160 psi, ASME stamped and listed
by Underwriters Laboratories. The water heater shall be approved for low NOx and meet or exceed California rule 1146.2. The unit shall provide modulating fire for smooth system operation and precise temperature control. Controls shall include: high temperature limit control (manual reset), upper and lower thermostats, modulating control, combination temperature and pressure gauge, low water cutoff, ASME rated temperature relief valve, drain valve and draft regulator. Control compartment door shall be hinged for easy access. The heater(s) shall be equipped with multiple anodes for cathodic protection. The heater(s) shall be insulated with
SUGGESTED SPECIFICATIONS
TITANTM LV POWER OIL AND DUAL FUEL (MODELS TPO AND TPD)
Water heater(s) shall be Model_____________________as manufactured by the State Water Heaters or an approved equal. Heater(s) shall have a minimum oil firing
rate of_____gallons per hour, an input rating of____________BTU/HR. The heater(s) shall have a recovery rate of_____GPH at a 100°F rise and a storage capacity
of______gallons. The 160 psi design pressure tank shall be
shall be equipped with______NPT water inlet and outlet openings, (2) 3˝ handhole cleanouts, and carry a National Board stamping. The heater(s) shall be ASME and the
entire unit listed by Underwriters Laboratories. Controls shall include: high temperature limit control (manual reset), upper and lower thermostats, combination temperature and pressure gauge, low water cutoff, ASME rated temperature and pressure relief valve, and barometric draft regulator. Control compartment door shall be hinged for easy access and include cam locks for security. The heater(s) shall be equipped with multiple anodes for cathodic protection. The heater(s) shall be insulated with
The TPO models shall have a UL listed burner with
The TPD models shall include a dual fuel burner with
In keeping with our policy of continuous product improvement, specifications are subject to change without prior notice.
COMMERCIAL 500 Lindahl Parkway, Ashland City, TN 37015 • www.statewaterheaters.com Printed in U.S.A.
The Expert’s Choice® | ©2003 State Water Heaters | STPBGODF/1003 |