Figure 7.

NSF Leg Kit

Figure 8.

The NSF Leg Kit (part number 9008214005) is needed only for applications that must conform to NSF/ANSI Standard 5. The installed height of the water heater will increase by 3" (7.6 cm) when the leg kit is installed. Follow these steps to install the Leg Kit. Use caution to prevent damage to the unit when installing the Leg Kit

1.Lift, tilt or lay the unit on its side to access the bottom of the legs.

2.Position the extension under leg aligning the holes in the leg extension with the holes in the leg. Assemble the bolt, bevel washers, flat washers, and nut through the aligned holes in the leg and leg extension as shown in Figure 8.

3.Once in place, tighten the nut and bolt assembly. Torque to 70 ft.lbs (9.67 kgf-m).

4.Insure that all four nut and bolt assemblies are torqued to the specified value before placing the unit on the floor.

Insulation Blanket

Breathing Hazard - Carbon Monoxide Gas

Do not obstruct water heater air intake with insulating blanket.

Gas and carbon monoxide detectors are available.

Install water heater in accordance with the instruction manual.

Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identification of components mentioned below. Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

DO NOT apply insulation to the front of the combustion chamber flange plate to insure that the spark igniter, flame sensor, and sightglass remain uncovered.

DO NOT cover the gas valve or the Temperature-Pressure Relief Valve.

DO NOT apply insulation within 5” (13 cm) of the blower, to insure the safe operation of the blower assembly.

DO NOT apply insulation on the control box that encloses the thermostat, ignition control, and variable frequency drive.

DO NOT cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.

DO inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

Hard Water

Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.

See the Maintenance Section in this manual for sediment and lime scale removal procedures.

Circulation Pumps

A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps.

See the Circulation Pump Wiring Diagrams (Figure 9.) in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1.

All-bronze or stainless steel circulating pumps are recommended for use with commercial water heaters.

10

Page 10
Image 10
State Industries SBL85 390NE(A), SBL85 275NE(A), SBL95 199NE NSF Leg Kit, Insulation Blanket, Hard Water, Circulation Pumps