Table 6. TECHNICAL DATA VENTING

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. 2006.

MODEL SBL95 199NE

Input: 199,000 Btu/hr

 

 

 

 

Total Vent Height (Feet)

 

 

 

Vent Connector Size: 6 inches

 

 

 

6

8

 

10

15

20

30

50

100

 

Input Btuh/hr

Rise

 

 

 

Vent Connector Diameter (Inches)

 

 

199,000

1 Ft.

 

7

7

 

7

6

6

6

6

6

 

199,000

2 Ft.

 

7

7

 

6

6

6

6

6

6

 

199,000

3 Ft.

 

6

6

 

6

6

6

6

6

6

Number of 199 Heaters

Combined Input in

 

Manifold and Common Vent Diameters (Inches)

 

Thousands of Btu/hr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

398,000

 

 

7

7

 

7

6

6

6

6

6

3

597,000

 

 

7

7

 

6

6

6

6

6

6

4

796,000

 

 

6

6

 

6

6

6

6

6

6

18