Troubleshooting

COMPLAINT

CAUSE

REMEDY

USER

Qualified Service Agency

*Water not hot enough

Thermostat set too low.

Set thermostat dial to a higher

 

 

 

temperature

 

 

Upper and/or lower temperature

Call qualified service agency

Check continuity and resistance (Ohms)

 

probe out of calibration.

 

of upper and lower temperature probes.

 

 

 

Replace probes if out of specification.

*Insufficient hot water

Thermostat set too low.

Set thermostat dial to a higher

 

*See WATER TEMPERATURE

 

temperature

 

CONTROL WARNING (on page

Upper and/or lower temperature

Call qualified service agency

Check continuity and resistance (Ohms)

12).

probe out of calibration.

 

of upper and lower temperature probes.

 

 

 

Replace probes if out of specification.

 

Main manual gas shutoff valve

Open main manual gas shutoff

 

 

partially closed.

valve to fullest extent.

 

 

Heater too small for demand.

Space usage to give heater time

 

 

 

to restore water temperature.

 

 

Heater recovery is slower.

Call qualified service agency

Check gas input. If incorrect, check

 

 

 

for inlet air blockage and/or flue gas

 

 

 

exhaust blockage.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a lower setting.

 

Rumbling.

Sediment accumulation on

Drain a quantity of water through

Delime heater.

 

bottom of tank.

drain valve. If rumbling persists,

 

 

 

call a qualified service agency.

 

Ticking or metallic sounds.

Expansion and contraction -

 

 

 

normal.

 

 

Pounding or water hammer.

Air chambers in piping have

Drain piping system and refill.

Follow the manufacturer's instructions

 

become waterlogged. Thermal

Heater must be off while this

for proper charging of the thermal

 

expansion tank damaged,

is being done. Check thermal

expansion tank.

 

improperly charged, or

expansion tank charge pressure

 

 

improperly sized.

when the water system pressure

 

 

 

is zero.

 

Water leaks.

Drain valve not closed tightly.

If drain valve cannot be closed

 

 

 

tightly, replace.

 

 

If leakage source cannot be

Shut off gas supply to heater

Repair or in case of suspected tank

 

corrected or identified, call

and close cold water inlet valve

leakage, be certain to confirm before

 

qualified service agency.

to heater.

replacing heater.

Gas odors.

Possible gas leaks.

Shut off gas supply to heater

 

 

 

and call gas company at once

 