•SYSTEM BACKUP

SYSTEM BACKUP

SERVICE MENU

MAIN MENU

SYSTEM SETUP

(System Setup Screen)

This screen allows the operator to set alarm and password features.

ALARM OFF DUR is the amount of time (0-99 minutes) that the alarm and horn will stay off after the alarm silence button is pushed. (When this function is set to 0, this feature will never turn off. When it is set to 99, it will stay off until another alarm occurs.)

OPER PW is the four (4) digit number that allows access to the station and pump status screen and the station operator screen. (When this feature is set to 0000 these screens are not password protected.)

OPER PW DUR is the amount of time (5-99 minutes) the password will allow access to the associated screens. The screen changes to the station status screen when the time expires.

SETUP PW is the four (4) digit number that allows access to the setup screens. (When this is set to 0000 there is no password protection).

Note: Factory default is Supervisor security enabled. Supervisor password is 1234.

SETUP PW DUR is the amount of time (5-99) the password will allow access to the associated screens. When the time expires, the screen changes to the station status screen.

LOW LEVEL DETECTION SETUP

Large Dehumidifying Dryers

Controls