Walls or Obstructions

Walls or Obstructions

The unit should be located so that air may circulate freely and not be recirculated. For proper air flow and access all sides of the unit should be a minimum of “W” away from any wall or obstruction. It is preferred that this distance be increased whenever possible. Care should be taken to see that ample

room is left for maintenance work through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit.

Multiple Units

For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is 4 feet.

Units in Pits

The top of the unit should be level with the top of the pit, and side distance increased to “2W”.

Decorative Fences

If the top of the unit is not level with the top of pit, dis- charge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement.

Fences must have 50% free area, with 1 foot undercut, a “W” minimum clearance, and must not exceed the top of

unit. If these requirements are not met, unit must be installed as indicated for “Units in pits”.

* “W” = Total width of the fluid cooler.

10

Page 10
Image 10
Sterling SC3-600, 25001301 warranty Walls or Obstructions, Multiple Units, Units in Pits, Decorative Fences

FAQ

What is the minimum distance required between units?

For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is 4 feet.

What are the requirements for decorative fences?

Fences must have 50% free area, with 1 foot undercut, a W minimum clearance, and must not exceed the top of the unit. If these requirements are not met, the unit must be installed as indicated for Units in pits.

What should be the top level of the unit when installed in a pit?

The top of the unit should be level with the top of the pit, and the side distance increased to 2W.