Sterling 60 cfm, 30 cfm Process Air Dew Point Display, Optional, Setting the High Dew Point Alarm

Models: 30 cfm

1 50
Download 50 pages 57.96 Kb
Page 25
Image 25
Process Air Dew Point Display

Figure 7: Settings for Process Temperature Controller (E5CN), Part No. A0567917

Mode

Parameter

Setting range

Default

Manuf. setting

Operation

Run/Stop

Run/Stop

Run

-

Alarm value 1

-1999 to 9999

0

25

 

Mode

Parameter

Setting range

Default

Manuf. setting

 

AT execute/cancel

ON, OFF

OFF

Various

Adjustment

Temperature input shift

-199.9 to 999.9

0.0

-

Proportional Band

0.1 to 999.9

8.0

Various

 

Integral Time

0 to 3999

233

Various

 

Derivative Time

0 to 3999

40

Various

Process Air Dew Point Display

Optional

The Process Air Dew Point meter indicates the current process air delivery moisture content. Standard dryers use a microprocessor-based controller for displaying dew point air temperature. The controller is a modular, self-contained unit removable from the mounting housing. All parameters are factory set and adjusted; normally, no field adjustment to the internal controls are necessary.

Figure 8: Typical Dew Point Display Monitor – Part No. A0555757

 

PV

 

 

SV

 

 

 

OUT1

 

 

 

OUT2 MANU STOP

RMT

AT

SUB1

AT

 

 

 

OMRON

 

 

E5CK

Note: No field adjustment is required. The dew point meter is meant for moisture indication only!

Setting the High Dew Point Alarm

The high dew point alarm setting is changed by pressing the up and down keys to input the alarm value. The factory setting for Alarm Value 1 (AL-1) is -10°F (-23°C).

Restoring the Process Air Dew Point Meter (E5CK) to Factory Setup

If the preset parameters on the controller have been tampered with and it no longer functions properly, call the Service Department. This controller is not meant to be modified.

15, 30, & 60 cfm Compact Dryers

25

Page 25
Image 25
Sterling 60 cfm, 30 cfm Process Air Dew Point Display, Optional, Typical Dew Point Display Monitor - Part No. A0555757