Pump Fault

If the pump verify signal is not present after the pump is started, the alarm horn/light will activate. The pump will be stopped and set to an offline condition. The Status screen will display “PMP FLT.” Pressing F2 while the status screen is displayed will silence the alarm.

Filter Can

If the filter can limit switch signal is not present after the pump is started, the alarm horn/light will activate. The Status screen will display “FLTR CAN”. Pressing F2 while the status screen is displayed will silence the alarm.

General Fault

If the general fault signal is present after the pump is started, the alarm horn/light will activate. The pump will be stopped and set to an offline condition. The Status screen will display “GEN FLT.” Pressing F2 while the status screen is displayed will silence the alarm.

All Faults

If after silencing an alarm, the condition remains beyond the time specified for ALARM SILENCE DURATION, the alarm horn/light will reactivate. Pressing F2 from the status screen will silence the alarm.