SITE REQUIREMENTS

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1.FLUE AND CHIMNEY REQUIREMENTS

1.1The chimney or flue system must comply with the rules in force, and must be a minimum of 127mm in diameter. (5").

1.2The minimum effective height of the flue or chimney must be 3 metres (10ft). Any horizontal flue run from the rear outlet should not exceed 100mm from the back of the appliance.

1.3The chimney or flue must be free from any obstruction. Any damper plates should be removed or secured in the fully open position, and no restrictor plates should be fitted.

1.4The chimney should be swept prior to the installation of the appliance. However, where it can be seen that the chimney is clean and unobstructed throughout its entire length, it need not be swept.

1.5If it is intended to fit the stove into a existing brick built chimney, a 5" (127mm) liner must be used. Larger lined flues may work, but in some instances could cause cold start flue problems resulting in nuisance shutdown. Lined flues above 7" (175mm) are not recommended.

1.6Due to recent changes to European chimney standards, new flue’s and chimney’s are now described by their temperature, pressure and resistance to corrosion, condensation and fire. To assist in identifying the correct flue system, the minimum flue specification is shown in the technical specification on page 8 of this book. Existing chimney’s are not covered by this system.

2.VENTILATION

2.1Consult the rules in force.

Note: This appliance does not normally require any additional ventilation when installed in G.B.

3.INSTALLATION OF THE GAS SUPPLY

3.1Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible.

3.2Ensure that the gas supply is capable of delivering the required amount of gas, and is in accordance with the rules in force.

3.3Soft copper tubing and soft soldered joints can be used but must not be closer than 50mm to the base of the tray.

3.4A means of isolating the gas supply to the appliance must be provided independent of any appliance control.

3.5All supply gas pipes must be purged of any debris that may have entered, prior to connection to the appliance.

4.APPLIANCE LOCATION

4.1This appliance must stand on a non-combustible hearth that is at least 12mm thick, and project a minimum of 50mm from the base of the stove in all directions. See diagram 1.

1

A = 581mm

B = 373mm

C = 12mm

4.2This appliance must not be installed in a room that contains a bath or shower.

4.3The stove is not suitable for installation against a combustible wall; all combustible materials must be removed from the area behind the stove.

4.4Ensure that all minimum clearances to combusible materials are complied with. See diagram 2 & 2A.

2

150

225

150

 

 

781 AR0522

2A

In a non-combustible recess attention must be given to allowing adequate clearance at the sides and rear of the stove, so that a spillage test can be performed, and the controls reached.

9