including the battery. If after the fuse replacement and after
3.6.2 Connection to the 230Vac-consumer appliances (AC OUTPUT)
The 230V consumer appliances must be connected to the terminals AC OUTPUT with cables which cross section has to follow the local rules in force (usually 2.5mm2). Connections are marked as follows “N“ Neutral, “PE“ Earth (connected to the appliance box), “L“ Live.
Caution: High voltages can be there. Make sure that the
3.6.3 Connection to the 230Vac Input (AC INPUT)
The
3.6.4 Connection to Auxiliary Contact
This contact is a potential free change over contact the currents and voltages allowed for this contact are max. 16A/250Vac. The LED 5 “Contact active” shows the position of them: alight mind active and off mind
3.6.5 Connection to Remote control
The Remote Control
The length of the cable for Remote Control should not exceed 40m. We deliver it with 20m cable.
3.6.6Connection to Temperature Sensor (Temp.)
The temperature sensor
3.6.7 Connection to the Remote Control for the „Power Sharing“
This remote control is connected with a 20m long cable and a RJ11/6 connector in the connection terminal „F“ (Temp. sensor). It can be connected and disconnected at any time. Push in the connector softly until you hear the „click“ showing that the connector is locked. In case the remote control is connected together with the Temp. sensor, a short cable with a