FRAMING SPECIFICATIONS CONTINUED
TYPICAL INSTALLATION SEQUENCE
Back Wall of Chase/Enclosure Including Finishing Materials, If Any. Optional Outside Air Kit C
D
| B |
| A |
Square Housing Not | Rough Framing Face |
Used on 5500 Model | (Unfinished Shown) |
Note: If the Outside Combustion Air Kit is to be installed, it must be installed before the appliance is framed and enclosed in the finishing walls.
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
1. Construct the appliance framing. |
2. Route gas supply line to appliance location. |
3. Position the appliance. |
4. Install the vent system and exterior termina- |
tion. |
5. Field wire and install operating control switch. |
Install optional Forced Air Kit, if required |
Model No. |
| A | B | C | D | |
|
|
|
|
|
| |
in. | 57 1/2 | 36 | 40 3/4 | 29 | ||
|
|
|
|
| ||
mm | 1461 | 914 | 1035 | 737 | ||
| ||||||
|
|
|
|
|
| |
in. | 65 3/4 | 40 3/4 | 46 1/2 | 32 7/8 | ||
|
|
|
|
| ||
mm | 1670 | 1035 | 1181 | 835 | ||
| ||||||
|
|
|
|
|
|
Corner Installation
Figure 6
Optional | Note: If the Outside Combustion | |
Air Kit is to be installed, it must | ||
Outside Air Kit | ||
be installed before the appliance | ||
Back Wall of Chase/Enclosure | is framed and enclosed in the | |
Including Finishing Materials, If Any. | finishing walls. | |
|
6. Make connection to gas supply. |
7. Install optional Outside Combustion Air Kit, |
if required. |
8. Install the logs and rockwool. |
9. Install the optional glass doors/enclosure |
panel, if required |
10. Checkout appliance operation. |
11. Spillage Test and Safety Limit Switch |
Operation. |
12. Adjust burner to ensure proper flame |
B
A
4IN.
(103 MM)
Square Housing Not
Used on 5500 Model
Figure 7
|
|
| Model No. |
| A | B |
|
|
|
|
|
|
|
|
|
| in. | 36 | 15 1/2 | |
|
|
|
|
|
| |
|
|
| mm | 914 | 394 | |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| in. | 40 3/4 | 18 | |
|
|
|
|
|
| |
4 IN. |
| mm | 1035 | 457 | ||
|
| |||||
(103 MM) |
|
|
|
|
| |
|
|
|
|
| ||
Rough |
|
|
|
|
| |
Framing Face |
|
|
|
|
| |
(Unfinished Shown) |
|
|
|
|
|
Inside Chase Installation
appearance. |
The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, ply- wood, particle board or other hard surfaces, extending the full depth and width of the appli- ance. Be sure fireplace rests on a solid continu-
Optional | Back Wall of Chase/Enclosure | ||
or | Including Finishing Materials, If Any. | ||
Outside Air Kit |
|
| |
|
| B | |
| A | Rough | |
Square Housing Not | Framing Face | ||
(Unfinished Shown) | |||
Used on 5500 Model | |||
|
Note: If the Outside Combustion Air Kit is to be installed, it must be installed before the appliance is framed and enclosed in the finishing walls.
Model No. |
| A | B | |
|
|
|
| |
in. | 36 | 15 1/2 | ||
|
|
| ||
mm | 914 | 394 | ||
| ||||
|
|
|
| |
in. | 40 3/4 | 18 | ||
mm | 1035 | 457 | ||
| ||||
|
|
|
|
ous floor or platform with appropriate framing for support and so that no cold air can enter the room from under the fireplace.
The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.
Usually, no special floor support is needed for the fireplace, however, to be certain:
1. Estimate the total weight of the fireplace |
system and surround materials such as brick, |
Outside Chase Installation
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
stone, etc., to be installed. |
7