Display Brightness

DISPLAY BRIGHTNESS can be set through the menu system of the control (MENU, 6, 3). This option changes the intensity of the display. The possible choices are 25%, 50%, 75% and 100%.

About this Control

ABOUT THIS CONTROL can be accessed in the menu system (MENU, 6, 4). This option provides information about the control. In particular it tells the serial number of the control and the software version that the control is running.

Control On Battery Backup Version

This controller is similar to the AC Kryos Controller. The menu system and all features are identical. The only operational difference is if a power failure occurs, the control goes into battery backup mode. The Kryos control operates on 24 VAC power. As an option, however, the control can also operate on battery power to provide up to 72 hours of continuous service without AC power. The system is designed for full operational service during a power failure, including full solenoid valve operation. The battery backup system can be ordered from Taylor-Wharton and should be factory installed.

Differences between the regular Kryos and the battery backed Kryos:

Please see the chart below for the differences between the two systems.

 

Regular Kryos

Battery Backed Kryos

SOLENOID VALVE

24

VAC solenoid

12 VDC solenoid

Wall Transformer

24

VAC/ 40 Voltamps output

16.5 VAC/ 40 Voltamps output

Battery

None

17amp-hour

Battery Extension Cable

None

Connects battery to control board

Software

V4.0

V4.0

Control Board (1)

Black 2-pin solenoid valve

Red 2-pin solenoid valve plug &

 

plug

Red 3-pin battery plug.

(1)The control board for the battery backup is quite different than the control board for the regular Kryos in that a number of parts are either removed or changed. The best way to tell if the control is a battery backed unit or a regular unit is to look at the valve connector.

Operation

The software is designed such that if power is lost and a battery-backed control is in place, the control detects the loss of power and continues to operate from the battery. If power is lost, a “Battery Backup” message appears on the display, the alarm beeper sounds and the red LED starts to flash. After a short period of time (approximately 10 seconds) the display will go dark to conserve power, however the red LED will continue to flash and the beeper will continue to sound until it is muted. The display can be brought back at any time by pressing any button on the front panel.

The control will continue to monitor the system, record logs and operate the valve until the battery runs too low. Original specifications required that the battery run, fully operational, for at least 72 hours. Battery backup mode is treated by the control as an alarm condition. This means that the remote alarm will be triggered after a period of time as defined by the user.

Note: We strongly recommend that all Cryo-Storage systems be connected to a redundant alarm, a building alarm system or a dialer. This insures that someone is notified if an error condition persists.