4
CHAPTER 1 FPS1000 SERIES SPECIFICATIONS
Model FPS1000 FPS1000 FPS1000
V/I -24 -32 -48
24 32 48
29 38.4 58
33 26 17.25
40 31 21
V1 (V)
V2 (V)
I1 (A)
I2 (A)
V1
V2
Fig. 1: Rated output current vs output voltage
Vout (V)
I1 Iout (A)
I2
Notes:
*1: For cases where conformance to various safety standards (UL, EN etc.) is required,
to be described as 100-240Vac (50/60Hz).
*2: At 100/200Vac, rated load and 25˚C ambient temperature.
*3: Not applicable for the noise filter inrush current less than 0.2mS.
*4: Measured with JEITA RC-9131A 1:1 probe, 20MHz B.W.
*5: From 85~132Vac or 170~265Vac, constant load.
*6: From No-load to Rated load, constant input voltage. Measured at the sensing point in Remote sense.
*7: Remote sensing can compensate up to 1V drop on each load wire.
*8: Inverter shut down method. Reset by AC voltage recycle or by On/Off control.
*9: Derate Maximum output power by 10% for input voltage less than 100VRMS.
*10 For FPS 1000-12/P(S), when used not with FPS-S1U or FPS-T1U
racks, an EMI suppressor clamp should be attached to the AC cable,
as close as possible to the AC inlet, to meet class B.
FPS1000
-12
12
13.2
66
72
1V
2V
3V
4A
5W
6Input voltage / frequency range (*1) ---
7Maximum input current (at 100/200Vac) A
8 ---
9 (*2) %
10 (*3) A
11 mS
12 (*5) ---
13 (*6) ---
14 (*4) mV
15 ---
16 PPM/°C
17 (*7) V
18 (*9) ---
19 Series operation
(*10)
---
20 ---
21 (*8) V
22 ---
23 ---
24 ---
25 ---
26 ---
27 ---
28 ---
29 ---
30 ---
31 ---
32 ---
33 ---
34 ---
35 ---
36 ---
37 ---
38 ---
39 ---
40 ---
41 ---
42 ---
43 mA
44 Kg
45 ---
Rated output voltage 12 32 48
FPS1000 SERIES SPECIFICATIONS FPS1000-12 FPS1000-32 FPS1000-48
Output voltage range 10.5~13.2 28.8~38.4 43~58
Output voltage set point 12+/-1% 32+/-1% 48+/-1%
Maximum output power 864 992 1008
Maximum Output Current (Refer to Fig.1) 72 31 21
85~265Vac continuous, 47~63Hz, Single phase
12.0/6.0
Power Factor (Typ) >0.98 at 115/230V and maximum output power
Inrush current Less than 40A
Efficiency (Typ) 84/86% 84/86% 85/88%
Hold-up time 20mS typical at 100Vac input, rated output voltage and less than 80% of rated load.
Maximum line regulation 0.40%
Max load regulation 0.80%
Output Ripple and noise pk-pk 200 250 300
Temperature stability 0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temperature.
Temperature coefficient 200
Remote sensing Possible. Refer to Instruction Manual.
Parallel operation Possible. Refer to Instruction Manual.
Possible. Refer to Instruction Manual.
Over current protection 105~125% of maximum output current. Refer to Fig. 1
Over voltage protection 31~34 41.5~45.5 62~66
Over temperature protection Inverter shut down method, automatic reset.
Remote On/Off control By electrical signal or dry contact. ON: 0~0.6V or short. OFF: 2~15V or open.
DC OK signal Open collector signal. On when Vout>80+/-5% rated output. Max.sink current: 10mA
Over-Temp. warning Open collector signal. Refer to Instruction Manual
AC fail signal Open collector signal. Refer to Instruction Manual
Auxiliary power supply 11.2~12.5VDC. 0.25A Maximum output current.
Vout voltage trimming Possible, via Vout Trim pin in the I/O connector. Refer to Instruction Manual.
Front panel indicators AC OK, DC OK, DC FAIL
I2C Interface Optional. Refer to Instruction Manual.
Operating temperature-models without IEC inlet
models with IEC inlet
0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate 2.5%/°C, 60°C to 70°C.
Storage temperature -30~85°C
Operating humidity 10~90% RH, no condensation.
Storage humidity 10~95% RH, no condensation.
Cooling By internal Fans. Variable speed control.
Vibration Built to meet ETS 300 019
Shock Built to meet ETS 300 019
Conducted emission EN55022B, FCC part 15J-B, VCCI-B
Radiated emission EN55022B, FCC part 15J-B, VCCI-B
Applicable safety standards UL60950-1, EN60950-1
Withstand voltage Input-Output:3000Vrms, 1 min. Input-Ground:2000Vrms, 1min. Output-Ground: 500Vrms,1min.
Insulation resistance More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc
Leakage current Less Than 1.1mA at 230Vac
Weight (Typ) 2.0
Size (W*H*D) 127x41x290mm. Refer to Outline Drawing.
24
FPS1000-24
21.5~29
24+/-1%
960
40
81/83%
150
14.3~15.7
0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C.
---