4.11 Remote Sensing
The Remote sensing compensates voltage drop on the load wiring. The maximum voltage drop on each wire is 1V,
however, it is recommended to minimize the voltage drop on the load wires to improve the response to load current
changes.
In case that the sensing wires are long, use separate twisted pair wires for the sensing and for the load wires to
minimize noise pick-up.
It is recommended to connect electrolytic capacitors in the following locations:
1) Across the load terminals
2) Between the "+S" terminal and the "+V" terminal of the power supply.
3) Between the "-S" terminal and the "-V" terminal of the power supply.
Refer to Fig 4-6 for typical connection of remote sensing.
LOAD
FPS1000
+V
+S
-S
-V
8
13
1,2,4
3,5,6
+
+
+
-
FPS1000 Instruction Manual