All installations and services must be performed by qualified personnel.
| Recommended |
Heating Capacity | Water Flow Rates |
(btuh) | for Heating |
| (GPM) |
40,000 | 4 |
60,000 | 6 |
80,000 | 8 |
100,000 | 10 |
DUCT SYSTEM
The duct system and load sizing calculation should follow the design standards of Air Conditioning Contractors of America (ACCA) - manuals D & J - or the American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) Latest Edition Fundamentals Volume.
To aid you in evaluating existing duct systems quickly, review the chart on Page 11 which shows the CFM capacity for square inch areas, based on .10" wc static pressure (SP) loss on the supply systems.
Each of the system's components (trunk lines,
The air handling capacity MUST BE EQUAL TO the supply system at a minimum when sizing the return air duct system. It is recommended to follow design parameters set down by ACCA or ASHRAE on the return air duct systems.
9