Thermo Products AH1-A, AH2-A service manual Cfm Capacity Charts

Models: AH1-A

1 22
Download 22 pages 23.58 Kb
Page 12
Image 12

All installations and services must be performed by qualified personnel.

CFM CAPACITY CHARTS

AH1-A

 

 

 

 

.2 Duct Static Pressure

 

 

 

 

with heating coil

 

 

 

 

And applicable Evaporator Coil Model

CFM (HI)

CFM (M. HI)

CFM (M. LOW)

CFM (LOW)

1024E and 1030E

1299

1123

992

821

1224-30G1

1756

1202

1073

880

1036E

1435

1231

1055

861

1236G1

1438

1193

1036

860

.2 Duct Static Pressure and applicable

 

 

 

 

Air Conditioning Coil Only

 

 

 

 

1024E and 1030E

1390

1243

1085

905

1224-30G1

1591

1335

986

921

1036E

1575

1307

1092

911

1236G1

1523

1280

1074

913

Heating coil

 

 

 

 

.2 Duct Static Pressure

1514

1261

1055

889

.2 Duct Static Pressure + .3 additional

 

 

 

 

load

1294

1109

964

785

AH2-A

 

 

 

 

.2 Duct Static Pressure

 

 

 

 

with heating coil

 

 

 

 

And Applicable Evaporator Coil Model

CFM (HI)

CFM (M. HI)

CFM (M. LOW)

CFM (LOW)

1060G1 and 1242G1

2052

1632

1326

1034

1042E

1915

1444

1296

1078

1048E

1568

1433

1251

1054

.2 Duct Static Pressure and applicable

 

 

 

 

Air conditioning coil only

 

 

 

 

1060G1 and 1242G1

2371

1826

1487

1517

1042E

1794

1580

1377

1132

1048E

1717

1515

1400

1122

Heating coil only

 

 

 

 

.2 Duct Static Pressure

2161

1685

1330

1047

.2 Duct Static Pressure + .3 additional

 

 

 

 

load

1977

1459

1200

962

CFM CAPACITY

The CFM at .2 static pressure takes into account the resistance of the internal A-coil. The CFM at a .5 static pressure accounts for the addition of an external hydronics coil which would typically add .3 to the static pressure.