Thermo Products MO-425 Supply air duct sizing Example, Heating Cfm Heat Output Of Furnace Btuh

Models: MO-425

1 20
Download 20 pages 49.62 Kb
Page 10
Image 10
Fig. 8: Supply air duct sizing Example

All installations and services must be performed by qualified service personnel.

Fig. 8: Supply air duct sizing Example

The RETURN AIR DUCT SYSTEM should equal the warm air duct system in airflow capabilities.

NOTE: When a return register is located in the same room as the furnace, the register must be at least 20 feet away from the furnace.

SIZING THE DUCT WORK FOR A COMBINATION HEATING AND COOLING SYSTEM:

Two formulas must be used in determining the CFM requirements of a combustion heating and cooling system.

1.HEATING CFM:

HEAT OUTPUT OF FURNACE (BTUH)

1.1 X TR (TEMPERATURE RISE, °F) = HEATING(CFM)

EXAMPLES:

A. 110,000 BTUH OUTPUT

1.1X 85°F TR = 1176 CFM FOR HEATING B. 110,000 BTUH OUTPUT

1.1X 70°F TR = 1429 CFM FOR HEATING

2.COOLING CFM: 400 CFM X COOLING TONNAGE (12,000 BTUH PER TON)=AIRFLOW FOR COOLING(CFM)

EXAMPLES:

A.400 CFM X 3 TON (12,000 BTUH) = 1,200 CFM FOR COOLING 1TON

B.400 CFM X 2.5 TON (12,000 BTUH) = 1,000 CFM FOR COOLING 1 TON

IMPORTANT: SIZE THE DUCT SYSTEM FOR THE LARGER OF THE TWO AIRFLOW REQUIREMENTS