All installations and services must be performed by qualified service personnel.
Yes |
|
|
|
| ||
|
|
|
| No |
|
|
IS IGNITION ESTABLISHED? |
| No |
| |||
|
|
| ||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
| ARE THE ELECTRODES |
| |||
|
|
|
| |||
|
| ARCING? |
|
|
| |
|
|
|
|
|
|
|
IS THE NOZZLE AND | No | POSITION THEM PER |
CAD CELL POSITIONED |
| BURNER MANUFACTURERS |
| ||
PROPERLY? * |
| INSTRUCTIONS |
|
|
|
Yes
Yes
Yes
IS IGNITION TRANSFORMER | No |
CAPABLE OF PRODUCING A |
|
3/4" ARC? (10,000 VAC) |
|
ARE THE ELECTRODES ALIGNED CONTACT SPRINGS TOUCHING ELECTRODE RODS, & PORCELAIN CLEAN AND UNCRACKED?
REPLACE IGNITION
TRANSFORMER
IS THE OIL PUMP
OPERATING?
Yes |
PERFORM CAD CELL CHECK
OUT ON PAGE 17.
IS THE COUPLING BETWEEN | No |
| REPLACE PUMP | |||
THE BURNER MOTOR AND |
|
| ||||
| ||||||
| THE PUMP STRIPPED? |
|
|
| ||
|
|
|
|
|
|
|
|
| Yes |
|
|
| |
|
|
|
|
|
| |
| REPLACE COUPLER |
|
|
|
| |
|
|
|
|
|
|
|
FURNACE OPERATES FOR
COMPLETE CYCLE?
No
BURNER RUN NORMAL
CYCLE?
Yes |
BLOWER RUNS
NORMAL CYCLE?
No
No
|
|
|
IS HEAT ANTICAPATOR SET | No | MEASURE MILLIAMPS BETWEEN 'W' &'R' |
TO MILLIAMP SETTING |
| ON THE T'STAT SUBBASE AND SET HEAT |
| ||
MEASURED ON SUBBASE? |
| ANTICIPATOR ACCORDINGLY |
|
|
|
|
|
|
Yes
IF PROBLEM PERSISTS CONTINUE TO NEXT SECTION.
| IS AIR TEMPERATURE RISE | No | ||||
| APPROX. 70 DEGREES F? |
|
|
| AND RETURN AIR TEMPERATURE | |
|
|
|
|
|
|
|
|
| Yes |
| |||
|
|
|
|
| ||
CHECK FAN ON & OFF SETTINGS |
|
| ||||
| ON FAN & LIMIT CONTROL |
|
| |||
|
|
|
|
|
|
|
* ALSO PERFORM CAD CELL CHECK OUT PROCEDURE(REFER TO INDEX).
14