EFFECTS OF PRESSURE ON NOZZLE FLOW RATE

All installations and services must be performed by qualified service personnel.

Yes

DOES FURNACE OPERATE

No

WITHOUT CONDENSING?

IS STACK TEMPERATURE No

ABOVE 350 DEGREES F?

Yes

HAS THE BURNER COMBUSTION BEEN SET AS INDICATED IN ABOVE SECTION?

Yes

IS THE TEMPERATURE DIFFERENCE BETWEEN SUPPLY AND RETURN AIR 70 DEGREES F OR MORE?

No

No

GO TO PROPER COMBUSTION ACHIEVED SECTION ABOVE AND SET COMBUSTION

ADJUST BLOWER SPEED TO RAISE TEMPERATURE RISE.

Yes

Yes

--INCREASE LENGTH OF BURNER ON CYCLE

--INSULATE CHIMENY WITH CHIMNEY LINER.

TROUBLE SHOOTING ENDS.

REPEAT PROCEDURE UNTIL TROUBLE FREE OPERATION IS OBTAINED.

EFFECTS OF PRESSURE ON NOZZLE FLOW RATE

NOZZLE

NOZZLE FLOW RATES IN

RATING

GALLONS PER HOUR (Approx.)

AT

80PSI

120PSI

140PSI

100 PSI

 

 

 

 

.50

0.45

0.55

0.59

.65

0.58

0.71

0.77

.75

0.67

0.82

0.89

.85

0.76

0.93

1.00

.90

0.81

0.99

1.07

1.00

0.89

1.10

1.18

1.10

0.99

1.21

1.30

1.20

1.07

1.31

1.41

1.25

1.12

1.37

1.48

 

 

 

 

NOZZLE

NOZZLE FLOW RATES IN

RATING

GALLONS PER HOUR (Approx.)

AT

80 PSI

120 PSI

140 PSI

100 PSI

 

 

 

 

1.35

1.21

1.48

1.60

1.50

1.34

1.64

1.78

1.65

1.48

1.81

1.95

1.75

1.57

1.92

2.07

2.00

1.79

2.19

2.37

2.25

2.01

2.47

2.66

2.50

2.21

2.74

2.96

2.75

2.44

3.00

3.24

3.00

2.69

3.29

3.55

 

 

 

 

16