Thermo Products OH8FA119D60B Heating Speed Set-ups, OH6FA072DV4, Furnace Motor Current

Models: OH6FA072D48R OH8FA119D60B OH6FA072DV4B OH8FA119DV5B OH6FX072DV4R OH6FA072DV4R OH6FA072DV4N OH6FA072D48N OH6FA072D48B OH8FA119D60R OH8FA119DV5R

1 78
Download 78 pages 920 b
Page 31
Image 31

Heating Speed Set-ups

OH6FA072DV4

 

 

 

 

 

Furnace Motor Current

 

 

 

 

 

Draw (Amps/ / Watts) vs.

 

 

 

 

 

External Static Pressure (in W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

Low Fire

Med Fire

High Fire

 

 

 

 

 

BTUH

60,000

72,000

90,000

Static Pressure (Amps/Watts)

 

 

Fan

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

SW 1

 

 

 

 

 

 

 

 

Switch

Heating

Aprox. Rise

Aprox. Rise

Aprox. Rise

 

 

 

 

Settings

CFM

(F0 )

(F0 )

(F0 )

0.2

0.5

 

 

3-OFF

740

75o

 

 

1.1/98

1.8/173

 

 

 

 

 

 

2-OFF

 

 

 

 

 

 

 

 

1-OFF

 

 

 

 

 

 

 

 

3-OFF

812

68o

82o

 

1.3/114

2.1/193

 

 

 

 

 

2-OFF

 

 

 

 

 

 

 

 

 

 

 

1-ON

 

 

 

 

 

 

 

 

3-OFF

883

63o

76o

 

1.5/129

2.4/218

 

 

 

 

 

2-ON

 

 

 

 

 

 

 

 

 

 

 

1-OFF

 

 

 

 

 

 

 

Factory

3-OFF

 

57o

69o

86o

 

 

 

SW1 Switch

968

1.7/148

2.4/223

 

2-ON

 

Settings

1-ON

 

 

 

 

 

 

 

 

3-ON

 

 

 

 

 

 

 

 

1054

 

63o

79o

1.9/173

2.7/246

 

 

2-OFF

 

 

 

1-OFF

 

 

 

 

 

 

 

 

3-ON

1153

 

58o

72o

2.3/207

3.0/283

 

 

2-OFF

 

 

 

 

 

 

 

1-ON

 

 

 

 

 

 

 

 

3-ON

1267

 

 

66o

2.7/247

3.5/332

 

 

2-ON

 

 

 

 

1-OFF

 

 

 

 

 

 

 

 

3-ON

1424

 

 

58o

3.4/315

4.3/409

 

 

2-ON

 

 

 

 

1-ON

 

 

 

 

 

 

 

 

 

= Recommended Heating Speed Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 18-1: ECM blower motor speed chart