Thermo Products OH8FA119D60R Cooling Speed Set-ups OH6F*072DV4, External Static Pressure in W.C

Models: OH6FA072D48R OH8FA119D60B OH6FA072DV4B OH8FA119DV5B OH6FX072DV4R OH6FA072DV4R OH6FA072DV4N OH6FA072D48N OH6FA072D48B OH8FA119D60R OH8FA119DV5R

1 78
Download 78 pages 920 b
Page 34
Image 34
Cooling Speed Set-ups

Cooling Speed Set-ups

OH6F*072DV4

Furnace Motor Current

Draw (Amps / Watts) vs.

External Static Pressure (in W.C)

Air Flow

Static Pressure (Amps/Watts)

 

Fan

 

 

 

 

 

 

Control

 

 

 

 

 

 

SW 1

 

 

 

 

 

 

Switch

 

 

 

 

 

 

Settings

Clg. Tonage

Cool

Continuous

0.2

0.5

 

6-OFF

2

799

500

1.2/109

2.1/186

 

5-OFF

 

 

 

 

 

 

 

4-OFF

 

 

 

 

 

 

6-OFF

2.5

1017

508

1.8/160

2.5/230

 

5-OFF

 

 

 

 

 

 

 

4-ON

 

 

 

 

 

 

6-OFF

3

1210

605

2.4/220

3.3/308

 

5-ON

 

 

 

 

 

 

 

4-OFF

 

 

 

 

 

 

6-OFF

3.5

1404

702

3.2/305

4.2/409

 

5-ON

 

4-ON

 

 

 

 

 

Factory

 

 

 

 

 

 

SW1

6-ON

4

1622

799

4.6/443

5.7/560

Switch

5-OFF

 

 

 

 

 

Settings

4-OFF

 

 

 

 

 

NOTE: All information is approximate. Results will vary by installation.

Figure 18-3: Cooling blower motor speed chart