Thermo Products OH8FA119D60B, OH8FA119DV5R, OH8FA119D60R B. Venting, Rotation Of Front Flue Elbow

Models: OH8FA119D60B OH8FA119DV5B OH6FX072DV4R OH6FA072DV4N OH6FA072D48N OH8FA119D60R OH8FA119DV5R

1 79
Download 79 pages 47.9 Kb
Page 13
Image 13

The vent connector pipe between the furnace and chimney shall be of equal diameter as the flue outlet of the furnace. The vent connector pipe must be made of 24 gauge (or thicker) corrosion-resistant steel. The vent connector pipe should be as short as possible and installed so that it has a continuous rise from the furnace to the chimney. The horizontal length of a connector to a natural draft chimney or vent serving a single appliance shall not be more than 75 percent of the height of the vertical portion of the chimney or vent above the connector. Elbows should be minimized and the pipe should be joined with metal screws and supported by straps. All horizontal runs of vent connector pipe should be pitched upward a minimum of ¼ inch per foot of run. A thimble should be used to connect the vent connector pipe to the chimney so the pipe may be readily removed in case of inspection or replacement. See Fig. 6 on preceding page.

B. VENTING:

NOTE: On the OH6 & OH8 it is possible to rotate the flue elbow (which is factory installed for vertical discharge) 90° counter clockwise from the vertical position to adapt to various venting systems. The OH8 flue elbow can also be rotated 90° clockwise.

Notice: Blocked Vent Switch Installation

The blocked vent switch kit must be installed to comply with CAN STD B140.4 where applicable. For installation instructions see AOPS2687 kit.

χCAUTION MUST BE TAKEN NOT TO EXCEED 90° ROTATION (OF THE FLUE ELBOW) .

ROTATION OF FRONT FLUE ELBOW:

When an installation requires that the flue exit out the left or right (OH8 only) side casing, remove screw securing the 90 deg. elbow and rotate it 90°. Then, remove knock-out in side casing and extend vent through the opening.

A trim collar may be ordered from Thermo Products to hide the gap around the flue pipe. This trim collar, however, is not required for operation. Trim collar/gasket part numbers(s) 14121 / 330073 for OH6 and 14132 / 330006 for OH8.

The OH6 & OH8 may be vented through a standard correctly sized chimney.

The OH6 & OH8 may also be horizontally vented through a sidewall. Thermo Products has available the Field model FDVS-45/FOVP-415 and FDVS-67/FOVP-615 side wall vent kits for such applications. When installing the sidewall vent kits, outside combustion air must also be applied to the burner. The following table identifies application order information.

SIDE WALL VENTING APPLICATION ORDER INFORMATION

 

 

FIELD VENT TERMINATION

SIDE WALL VENT

COMBUSTION AIR INTAKE

 

 

KIT

ACCESSORIES KIT

HOOD KIT

 

(15’ application MAX)

(BURNER SPECIFIC)

(FOR COMBUSTION AIR

BURNER

APPLICATIONS ONLY)

THERMO PRODUCTS PART

THERMO PRODUCTS

 

THERMO PRODUCTS PART

 

 

NUMBER

PART NUMBER

NUMBER

 

(OH6)

(OH8)

 

 

Beckett AFG

AOPS8393

AOPS8414

AOPS8394

AOPS8397

 

 

 

 

 

Riello BF3

AOPS8393

AOPS8414

AOPS8395

AOPS8416

 

 

 

 

 

Beckett NX

AOPS8393

N/A

AOPS8412

AOPS8413

(OH6 ONLY)

 

 

 

 

Table 2: Sidewall vent kits

The Field vent kit is set up with 4 inch diameter vent pipe for OH6 and 6 inch diameter vent pipe for the OH8 with concentric through-the-wall vent termination/inlet air vent hood. The combustion air inlet pipe diameter is also 4 inch diameter. For Riello, the combustion air inlet pipe will be reduced to 3 inch diameter with the Riello sidewall vent kit. For Beckett, the combustion air inlet pipe will be reduced to 3” diameter with the Beckett sidewall vent kit.