Heat Mode

When a call for heat (“W”) is received from the thermostat, if the “Cool” mode is not already active, the “T-T” terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 (positions 1 and 2) select one of four blower on delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed is energized. The control remains in steady heat mode until the thermostat is satisfied. When the call for heat signal is removed, the “T-T” terminal is de-energized and the blower off delay is started. The on-off pattern of DIP switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed terminal is de-energized.

DIP SWITCH 2 SECTION STATE

BLOWER DELAY TIMES

 

1

2

3

4

Counter Flow

ON - SEC

 

OFF - MIN

ON - SEC

 

 

 

 

 

 

 

 

OFF

OFF

 

 

15

30

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

24

60

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

36

120

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

48

240

 

 

 

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

 

2

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

4

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

 

6

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

 

8

 

 

 

 

 

 

 

 

Table 11: ON and OFF Blower Delay Time Switch Settings

Motor Blower Speed

Three interconnected blower speed outputs are provided. A “G” call for fan will provide power to the LOW speed tap only. A “W” heat call will provide power to the Heat speed tap only. A “Y” cooling call will provide power to the Cool speed tap only.

In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W” inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to the control switching into a heating mode. In the case where the control is in a heating mode with both “Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a “Y” speed following the blower on delay for that call.

The speed taps are interconnected and interlocked, only one speed may be powered at any one time. When a speed is to be operated, the speed select relays are operated to select the path to the motor tap and then the enable relay is operated to switch the operating power to the selected motor speed tap. If the speed of the running motor is to be changed, first the enable relay removes power from the motor, the new speed is selected and then power is restored to the motor.

Blower On and Off Delays

Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer to Table 11 for specific delay values.

38

Page 41
Image 41
Thermo Products OH8FA119D60B, OH8FA119DV5R, OH8FA119D60R, OH6FA072D48N On and OFF Blower Delay Time Switch Settings

OH8FA119D60B, OH8FA119DV5B, OH6FX072DV4R, OH6FA072DV4N, OH6FA072D48N specifications

Thermo Products has established a reputation for delivering high-quality heating solutions tailored for various applications. Among their standout offerings are the OH8FA119DV5R, OH8FA119D60R, OH6FA072D48B, OH6FA072D48N, and OH6FA072DV4N models. These units are engineered with precision and incorporate advanced technologies to deliver reliable performance in residential and commercial settings.

One of the main features of these models is their energy efficiency. They utilize modern heat exchanger designs, which allow for maximum heat transfer while minimizing energy consumption. This not only helps in reducing utility bills but also supports sustainable practices by lowering the carbon footprint. Many systems are also equipped with variable-speed motors, providing precise airflow control, which enhances comfort while operating quietly.

In addition to their energy efficiency, these units incorporate smart technology that allows for seamless integration into home automation systems. This feature enables users to monitor and control their heating systems remotely through mobile apps, making it convenient to adjust settings for optimal comfort. The smart thermostats associated with these models often feature learning capabilities, which adapt to users' habits to optimize heating schedules further.

Durability is another standout characteristic of the OH8FA and OH6FA series. Built with robust materials, these heaters are designed to withstand the rigors of daily use. Many units come with extended warranties, reflecting the manufacturer's confidence in their longevity. Furthermore, corrosion-resistant components ensure that the units maintain their performance over time, even in challenging environments.

Safety is also a key consideration in these products. Equipped with multiple safety features, including overheat protection and flame sensors, users can rest assured their heating systems operate without risk. Additionally, these models often include advanced diagnostics, making troubleshooting easier and enhancing user experience.

In summary, Thermo Products' OH8FA119DV5R, OH8FA119D60R, OH6FA072D48B, OH6FA072D48N, and OH6FA072DV4N represent a blend of efficiency, technology, durability, and safety in heating solutions. Whether for a cozy home or a large commercial space, these models offer versatile options to meet diverse heating needs while prioritizing energy conservation and user convenience. As the demand for efficient heating continues to rise, Thermo Products remains a leader in providing innovative solutions that cater to modern heating requirements.