Thermo Products OHFA199DV5B A. Diagnostics, Diagnostic Features, B. Cad Cell Checkout Procedure

Models: OHFA199DV5R OHFA199DV5B

1 78
Download 78 pages 14.24 Kb
Page 62
Image 62
A. DIAGNOSTICS:

2.Make sure thermostat is calling for burner operation.

3.Check oil supply and make sure all valves are open.

A. DIAGNOSTICS:

To assist in troubleshooting this appliance, it is equipped with an integrated safety and ignition control with diagnostics. These diagnostics include an indicator light that relays the operational status of the control and can help in diagnosing the condition of the flame sensor.

Diagnostic Features:

The Honeywell brand model R7184B (or alternate R7184U) safety and ignition control module used on this unit continuously monitors the operation of the heating system. If an abnormal condition occurs, the LED light on the control will rapidly flash indicating the operational status of the unit. In event this control malfunctions, the entire control should be replaced. It is not field-repairable.

In the event of an operational failure of the burner system, the rate of flashes, if any, of the ignition control module LED should be noted, before turning off power to the unit. Otherwise, power to the heating section will be interrupted and the control LED will not furnish the diagnostic flashing. It may be necessary to restart the furnace and have the failure occur again. For the model R7184B, under normal operating conditions, the LED will be continuously lit while the burner is operating.

If either control has sensed a flame failure, which was uncorrected by initiating another trial-for-ignition, the control will cease ignition trials and shutdown the burner, or “lockout”. The LED will continuously flash at a high rate (approximately 1/2-second “on”; 1/2 second “off”, for the model R7184B.

Diagnostic Features:Number of flashesCad Cell Resistance (in ohms)Model R7184BB. CAD CELL CHECKOUT PROCEDURE:Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background: If the appliance fails to relight after resetting the primary control twice contact a qualified service company. DO NOT continue to reset primary control.

The operational condition of the flame sensor, or “cad cell”, can be checked by depressing the reset button on the control module, while the burner is operating. Count the number of flashes of the LED and compare them to the table below.

Number of flashes

Cad Cell Resistance (in ohms)

 

Model R7184B

1

0 to 400

2

400 to 800

3

800 to 1600

4

1600 ≤

If it is necessary to troubleshoot the flame sensor independently of the burner primary, the following procedure may be used.

B. CAD CELL CHECKOUT PROCEDURE:

1.Stop burner and shutoff electrical power to the appliance.

2.Open burner junction box (on top of the burner blower) and remove the plug-in portion of the cad cell by pulling it forward from and clear of the receptacle. Connect an ohmmeter across cad cell pins. With the cell exposed to direct room light, the measured resistance should be less than 2500 ohms (in fact, it may be less than 200 ohms).

59

Page 62
Image 62
Thermo Products OHFA199DV5B A. Diagnostics, Diagnostic Features, B. Cad Cell Checkout Procedure, Number of flashes