Before attempting to measure or adjust manifold gas pressure, the inlet (supply) pressure must be within the specified range for the gas being used both when the heater is in operation and on standby. Incorrect inlet pressure could cause excessive manifold gas pressure immediately or at some future time.
Instructions to Check Manifold Pressure:
1)With the manual valve (on the combination valve) positioned to prevent flow to the main burners, connect a manometer to the 1/8" pipe outlet pressure tap in the valve. NOTE: A ma- nometer
spring type gauge due to the difficulty of maintaining calibration of a spring type gauge.
2)Open the valve and operate the heater. Measure the gas pressure to the manifold. Normally adjustments should not be necessary to the factory preset regulator.
If adjustment is necessary, set pressure to correct settings by turning the regu- lator screw IN (clockwise) to increase pressure. Turn regulator screw OUT (counterclockwise) to decrease pressure.
Consult the valve manufacturer's literature provided with the heater for more detailed information.
11. Electrical Supply and Connections
All electrical wiring and connections, including electrical ground- ing MUST be made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in Canada, the Ca- nadian Electrical Code, Part
Check the rating plate on the heater for the supply voltage and current requirements. A separate line voltage supply with fused disconnect switch should be run directly from the main electri- cal panel to the heater. All external wiring must be within ap- proved conduit and have a minimum temperature rise of 60oC. Conduit from the disconnect switch must be run so as not to interfere with the service panels of the heater.
The electrical supply connects at the top back of the heater in the left corner (left when facing the back of the heater). A threaded hole is provided for a standard 1/2" electrical fitting.
The wiring access panel is easily removed for field connections. Consult the wiring diagram supplied with your heater. Replace the panel after the wiring connections are made.
If the heater has
A
Specific wiring diagrams that include standard and
WARNINGS: On a heater with a unit disconnect switch (Option
If you turn off the power supply, turn off the gas.
The operating sequence of the heater can be found on the heater wiring diagram and is pub- lished in Paragraph 24, Check Installation and
CAUTION: If any of the original wire as
supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105oC, except for limit control and sensor lead wires which must be 150oC. See Hazard Levels, page 2.
12. Thermostat and Thermostat Connections
A thermostat is not standard equipment but is an installation requirement. Use either an optional thermostat available with the heater or a
Field Wiring from Disconnect in Conduit
Threaded
Hole for
Standard 1/2"
Fitting
Note:
Remove
Access Panel to make connections
thermostat. Install according to the thermostat manufacturer's instructions. Make sure that the heat anticipator setting on the thermostat is in accordance with the amperage value noted on the
wiring diagram of your heater. Terminal Strip Connections - The standard heater is equipped with a two- screw terminal connector strip (See Fig-
ure 10) for easy connection to the low voltage controls (24V). When factory-
installed options require
If your heater requires field instal- lation of the
Figure 9A - Electrical Connections
structions packaged with the relay or thermostat option.