15. Blower Speed Adjustment

The blower speed may be adjusted to achieve the desired outlet tem- perature, as long as the adjustment is within the temperature rise and the static pressure limits shown on the heater rating plate. Direct drive motors are factory set as indicated in the chart below. Belt drive mo- tors are factory set at the mid-point between maximum and minimum blower speeds.

If the duct resistance is low, the blower may deliver too high an air volume; or if the heater is operated without ductwork, it may deliver sufficient excess air to overload the motor, causing the overload pro- tector to cycle the motor. Reducing the blower speed will correct these conditions. If ductwork is added to an installation, it may be necessary to increase the blower speed. Decreasing blower speed will increase outlet temperature; increasing blower speed will decrease outlet tem- perature.

Blower Model Sizes 25-100 with Direct Drive

Direct drive blower motors have multi-speed taps for speed adjust- ment. If your installation requires an adjustment of the blower speed, the motor may be re-wired to an alternate tap by following these in- structions.

1.Turn off the gas and the electric power.

2.Remove the left (left when facing the back of the unit) outer side panel of the heater to reveal the wiring connections.

3.Consult the wiring diagram on the heater and follow the below chart to choose the wire for the desired adjustment. The asterisk(*) indi- cates the factory-wired speed.

Model Size

Speed

Use these Two Motor Wires

25

*Medium

*Blue and White

 

Low

Red and White

50

*High

*Black and White

 

Medium

Blue and White

 

High

Black and White

75

*Medium

*Blue and White

 

Low

Red and White

 

*High

*Black and White

100

Medium

Blue and White

 

Low

Red and White

 

 

 

4.Cut the crimped cap from the end of the wire that you intend to use and strip the insulation.

5.Disconnect the factory-wired connection and re-wire, using the newly stripped wire.

6.Put a wire nut on the end of the blower motor wire that was discon- nected.

7.Replace the heater side panel and turn on the gas and the electric.

Blower Model Sizes 50-400 with Belt Drive

The belt drive on these units is equipped with an adjustable pulley which permits adjustment of the blower speed. Follow these instruc- tions to adjust the blower speed.

1.Turn off the gas and the electric power.

2.Loosen belt tension and remove the belt.

3.Loosen the set screw on the side of the pulley away from the motor.

4.To increase the blower speed, decreasing outlet temperature, turn the adjustable half of the pulley inward. To decrease the blower

speed, increasing the outlet temperature, turn the adjustable half of the pulley outward. One turn of the pulley will change the speed 8-10%.

5.Tighten the set screw on the flat portion of the pulley shaft.

6.Replace the belt and adjust the belt tension. Adjust tension by turn- ing the adjusting screw on the motor base until the belt can be de- pressed 1/2-3/4". (See Figure 13.) Re-tighten the lock nut on the adjusting screw.

7.Turn on the gas and electric. Light the heater following the instruc- tions on the lighting instruction plate.

8.Check the motor amps with an amp meter. The maximum motor amp rating on the motor nameplate must not be exceeded.

CAUTION: An external duct system static pressure not within the limits shown on the rating plate or improper adjustment of the motor pulley or belt may overload the motor.

16. Blower Rotation

Each blower housing is marked for proper rotation. Rotation may be changed on single-phase motors by re-wiring in the motor terminal box. Three-phase motors may be reversed by interchanging two wires on the 3-phase supply connections.

17. Fan Control

1.A fan control provides the following:

(a)Delay of fan or blower operation to prevent the discharge of cold air.

(b)Fan or blower operation as long as the unit is hot.

2.The fan control provides additional safety by keeping the fan or blower in operation in the event that the gas valve fails to close when the thermostat is satisfied.

3.To be sure that the fan or blower can continue to operate, the power supply to the heater MUST NOT be interrupted except when ser- vicing the unit.

4.If the customer wants the heater off at night, the gas valve circuit SHOULD BE OPENED by a single pole switch wired in series with the thermostat. Some thermostats are provided with this fea- ture.

Multiple units controlled from a single thermostat are shut off in the same manner. For proper operation, be sure the fan control wiring is observed.

WARNING: If you turn off the power supply, turn off the gas. See Hazard Levels, page 2.

NOTE: Low ambient temperatures (less than 40oF) may cause false cycling of the fan/blower. To prevent this, a time delay relay can be added to the unit (available with single-stage gas valve only) to acti- vate the fan/blower electrically independent of the heat exchanger or the room temperature. The low ambient fan control relay can be fac- tory installed; Option BF8 will appear on the heater wiring diagram. Or, the relay can be field installed; order Option CQ3 (P/N 112779). This relay is in addition to the fan control The fan control is a safety

device and should never be removed from the heater circuit.

18. Limit Control

All models are equipped with an automatic, non-adjustable reset limit control that acts to interrupt the electric supply to the redundant main operating valve in case of motor failure or lack of airflow due to re- strictions at the inlet or outlet.

Mfg P/N 98807 Rev 8, Page 17

Page 17
Image 17
Thomas & Betts BE, FE warranty Blower Speed Adjustment, Blower Rotation, Fan Control, Limit Control

BE, FE specifications

Thomas & Betts, a subsidiary of ABB, is renowned for its innovative electrical products and solutions, particularly in the fields of connectors, terminals, and wiring devices. Among its extensive product lineup, the FE and BE series stand out for their exceptional performance and versatility in various applications.

The FE (Flat Eye) and BE (Blank Eye) connectors are designed to provide reliable electrical connections in demanding environments. These connectors are particularly well-suited for industrial, commercial, and residential applications, ensuring that they meet the rigorous standards required in these fields.

One of the key features of the FE and BE connectors is their robust construction. Made from high-quality materials, they are resistant to corrosion, moisture, and other environmental factors that could compromise the integrity of the connection. The connectors are engineered to withstand high temperatures and mechanical stress, making them ideal for use in harsh conditions where reliability is essential.

Moreover, the design of FE and BE connectors facilitates easy installation and maintenance. The connectors come with user-friendly features such as a clear labeling system and intuitive locking mechanisms, ensuring a secure fit and minimizing the risk of connection failure. Additionally, these connectors are compatible with various wire sizes, offering flexibility for different projects.

Technologically, Thomas & Betts has integrated advanced manufacturing processes to ensure precision and consistency in the production of FE and BE connectors. This attention to detail results in products that not only meet but often exceed industry standards, providing customers with peace of mind regarding their electrical systems.

In terms of performance, the FE and BE connectors deliver exceptional conductivity, which is critical for minimizing energy loss and ensuring efficient operation in electrical systems. This characteristic is especially important in applications where energy efficiency and reliability are paramount.

In summary, Thomas & Betts FE and BE connectors embody a perfect blend of durability, ease of use, and technological advancement. Their robust design, compatibility with various wire sizes, and resistance to environmental stressors make them a preferred choice for professionals in the electrical industry. With a commitment to quality and innovation, Thomas & Betts continues to set the standard in electrical connectivity solutions, ensuring that their products remain at the forefront of the industry.