9. Venting (cont'd)

Venter Outlet Attachment Requirements:

If the pipe used in the vent run is larger than the diameter of the venter outlet (See Vent Length Table 2), make the transition at the venter outlet.

A minimum of 12" of straight pipe is required at the venter outlet (or transition fitting) before installing an elbow in the vent system. An elbow should never be attached directly to the venter. An elbow attached to the straight pipe can be in any position at or above horizontal. See Figure 5.

Figure 5 - Alternate Vent Directions (vent in any position above horizontal; minimum of 12" of straight pipe

required before an elbow)

2.Vent Pipe

If installed with a horizontal vent run, use either vent pipe approved for a Category III heater or appropriately sealed 26-gauge galva- nized steel or equivalent single-wall pipe.

If at least half of the equivalent length of the vent system is verti- cal, vent pipe approved for a Category I heater may be used. Single- wall pipe or double-wall (Type B) vent pipe are suitable for use with a Category I heater.

Use only one of the flue pipe diameters listed in the Vent Length Tables for the furnace size being installed.

2A. Vent Pipe Diameter Reduction

If at least half of the equivalent length of the vent system is verti- cal, the vent pipe diameter may be reduced one inch from the stan- dard diameter listed in Vent Length Table 1. Only single-wall pipe is suitable for use when reducing the pipe diameter. A taper-type reducer must be used. The maximum allowable vent length remains the same. If required, double wall pipe may be used at the terminal end as shown in Figure 6. (Use the equivalent length for elbows as shown in Vent Length Table 1 for the standard vent pipe diameter. All elbows used in the vent system must be considered.)

3.Vent Length Tables

Table 1: Maximum Permissible Vent Lengths

 

Vent Pipe

Maximum

 

Equivalent Straight

Model

Diameter

Vent Length*

 

Length** - ft (m)

 

-" (mm)

- ft (m)

 

90o Elbows

45o Elbows

25

4"(102)

30 ft (9.1 m)

 

3.5' (1 m)

1.8' (.5 m)

50

4"(102)

40 ft (12.2 m)

 

5' (1.5 m)

2.5' (.8 m)

75

4"(102)

50 ft (15.2 m)

 

7' (2.1 m)

3.5' (1.1 m)

100

4"(102)

50 ft (15.2 m)

 

7' (2.1 m)

3.5' (1.1 m)

125

5"(127)

50 ft (15.2 m)

 

5' (1.5 m)

.5' (.8 m)

165

5"(127)

50 ft (15.2 m)

 

9' (2.7 m)

4.5' (1.4 m)

200

5"(127)

50 ft (15.2 m)

 

8' (2.4 m)

4.0' (1.2 m)

250

5"(127)

50 ft (15.2 m)

 

10' (3.0 m)

5' (1.5 m)

300

6"(152)

50 ft (15.2 m)

 

11' (3.4 m)

5.5' (1.7 m)

400

6"(152)

50 ft (15.2 m)

 

15' (4.6 m)

7.5' (2.3 m)

Table 2: Optional Maximum Permissible Vent Lengths

(Requires an increase in vent pipe diameter.)

 

Vent Pipe

Maximum

Equivalent Straight

Model

Diameter

Vent Length*

Length** - ft (m)

 

- " (mm)

- ft (m)

90o Elbows

45o Elbows

100

5" (127)

60 ft (18.3 m)

8' (2.4 m)

4.0' (1.2 m)

165

6" (152)

60 ft (18.3 m)

10' (3.0 m)

5.0' (1.5 m)

200

6" (152)

60 ft (18.3 m)

12' (3.7 m)

6.0' (1.8 m)

250

6" (152)

70 ft (21.3 m)

8' (2.4 m)

4.0' (1.2 m)

300

7" (178)

70 ft (21.3 m)

13' (4.0)

6.5' (2.0 m)

400

7" (178)

90 ft (27.4 m)

14' (4.3)

7.0' (2.1)

*Note 1: If the system contains all vertical pipe or a combination of horizontal and vertical vent pipe, the Maximum Permissible Vent Length shown in Tables 1 and 2 may be increased one foot for each foot vertical rise up to a maximum increase of 10 feet for model sizes 25 thru 100 and up to 20 feet for model sizes 125 thru 400.

**Reduce the maximum vent length by the amount indicated for each elbow.

4.Vent System Joints

Vent system joints depend on the installation and the type of pipe being used.

If using single wall, 26-gauge or heavier galvanized pipe, secure slip- fit connections using sheet metal screws or rivets. Seal pipe joints ei- ther with tape suitable for 550oF (such as Option FA1, P/N 98266) or high-temperature silicone sealant.

If using Category III vent pipe, follow pipe manufacturer's instructions for joining pipe sections. When attaching Category III pipe to the ven- ter outlet or the vent cap, make secure, sealed joints following a proce- dure that best suits the style of Category III pipe being used.

If using double-wall (Type B) vent pipe (allowed only if 1/2 of the equivalent vent length is vertical), follow pipe manufacturer's instruc- tions for joining pipe sections. For joining double-wall pipe to the ven- ter outlet collar, single-wall pipe, and/or the vent cap, follow the in-

structions below.

Instructions for attaching double-wall (Type B) vent pipe to the venter out- let, a single-wall pipe run, or to the vent cap (use these instructions for ei- ther full length double-wall or terminal only):

Hardware and Sealant Required: 3/4" long sheetmetal screws; and a tube of RTV

1)Look for the "flow" arrow on the vent pipe; attach according to the arrow. Slide the pipe so that the venter outlet, the single-wall pipe, or the vent cap is inside the double-wall pipe.

2)Drill a hole through the pipe into the outlet collar, the single-wall pipe, or the vent cap. (Hole should be slightly smaller than the sheet metal screw being used.) Using a 3/4" long sheet metal screw, attach the pipe. Do not overtighten. Repeat, drilling and inserting two additional screws evenly spaced (120o apart) around the pipe.

3)Use RTV to seal any gaps. If there is an annular opening, run a large bead of RTV in the opening. The bead of RTV must be large enough to seal the opening, but it is not necessary to fill the full volume of the annular area.

5.Vent System Support

Support lateral runs every six feet, using a non-combustible material such as strap steel or chain. Do not rely on the heater for support of either hori- zontal or vertical vent pipe

6.Condensation

Single wall vent pipe exposed to cold air or run through unheated areas must be insulated. Where extreme conditions are anticipated, install a means of condensate disposal.

7.Vent Terminal (Pipe and Vent Cap)

The vent system must be terminated with a suitable vent cap that is the same size as the vent run.

Heaters installed in Canada must be equipped with the vent cap sup- plied as optional equipment by the heater manufacturer (Option CC1 or Option BT2). Heaters installed in the United States must be equipped with the heater manufacturer's vent cap, a Type L Breidert Air-x-hauster®vent cap, or equivalent. Use of a vent cap supplied by the pipe manufac-

Form 436, Page 8

Page 8
Image 8
Thomas & Betts FE, BE warranty Venting contd

BE, FE specifications

Thomas & Betts, a subsidiary of ABB, is renowned for its innovative electrical products and solutions, particularly in the fields of connectors, terminals, and wiring devices. Among its extensive product lineup, the FE and BE series stand out for their exceptional performance and versatility in various applications.

The FE (Flat Eye) and BE (Blank Eye) connectors are designed to provide reliable electrical connections in demanding environments. These connectors are particularly well-suited for industrial, commercial, and residential applications, ensuring that they meet the rigorous standards required in these fields.

One of the key features of the FE and BE connectors is their robust construction. Made from high-quality materials, they are resistant to corrosion, moisture, and other environmental factors that could compromise the integrity of the connection. The connectors are engineered to withstand high temperatures and mechanical stress, making them ideal for use in harsh conditions where reliability is essential.

Moreover, the design of FE and BE connectors facilitates easy installation and maintenance. The connectors come with user-friendly features such as a clear labeling system and intuitive locking mechanisms, ensuring a secure fit and minimizing the risk of connection failure. Additionally, these connectors are compatible with various wire sizes, offering flexibility for different projects.

Technologically, Thomas & Betts has integrated advanced manufacturing processes to ensure precision and consistency in the production of FE and BE connectors. This attention to detail results in products that not only meet but often exceed industry standards, providing customers with peace of mind regarding their electrical systems.

In terms of performance, the FE and BE connectors deliver exceptional conductivity, which is critical for minimizing energy loss and ensuring efficient operation in electrical systems. This characteristic is especially important in applications where energy efficiency and reliability are paramount.

In summary, Thomas & Betts FE and BE connectors embody a perfect blend of durability, ease of use, and technological advancement. Their robust design, compatibility with various wire sizes, and resistance to environmental stressors make them a preferred choice for professionals in the electrical industry. With a commitment to quality and innovation, Thomas & Betts continues to set the standard in electrical connectivity solutions, ensuring that their products remain at the forefront of the industry.