1800 Series User Manual

29

Warning

Warning

Display State

LED State

 

Alarm State

Description and Resolution

 

 

 

 

 

 

 

 

Low Battery

 

 

 

 

Warning/Fault Flash

Alarm will

The batteries have less than 30%

 

 

 

 

 

Backup

Flash

sound for

power remaining. The warning will

 

 

 

 

 

 

 

1-second at

continue until either the batteries

 

 

 

 

 

 

 

5- second

become completely exhausted or

 

 

 

 

 

 

 

intervals.

AC input power is restored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current Limit

 

 

 

 

Warning/Fault Flash

Alarm will

An output current limit warning is

(Over

 

 

 

 

80%

Flash

sound for

typically a sign of misapplication.

Current)

 

 

 

 

 

 

1/2- sec-

The load may not be appropri-

 

 

 

 

 

 

 

ond at

ate for UPS support. For further

 

 

 

 

 

 

 

1-second

explanation contact your Toshiba

 

 

 

 

 

 

 

intervals.

UPS service representative at 1-

 

 

 

 

 

 

 

 

877-867-8773 (outside the U.S. call

 

 

 

 

 

 

 

 

713-466-0277).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

Warning/Fault

Flash

Alarm will

The temperature of the UPS operating

Over Heat

 

 

 

 

100%

Flash

sound for

environment is too high. Causes of

 

 

 

 

 

 

 

1-second at

this condition include allowing the room

 

 

 

 

 

 

 

15- second

temperature to exceed 104°F (40°C), a

 

 

 

 

 

 

 

blocked vent, or direct sunlight on the

 

 

 

 

 

 

 

intervals.

 

 

 

 

 

 

 

unit. The unit will transfer to bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode until the temperature is reduced.

 

 

 

 

 

 

 

 

If temperature is not reduced after an

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

allowable time, the unit will shut down.

 

 

 

 

 

 

 

 

 