Toshiba 1800 manual Appendix A Specifications

Models: 1800

1 52
Download 52 pages 24.03 Kb
Page 38
Image 38
Appendix A: Specifications

Appendix A: Specifications

Model Number

UG1A1A015C6TB 1

UG1A1A020C6TB1

UG1A1A024C6TB1

UG1G2L024C6TB

 

 

 

 

 

 

Rated Capacity

1500VA (1.05KW)

2000VA (1.4KW)

2400VA (1.68KW)

2300VA (1.61KW)

 

 

 

 

 

 

 

 

 

 

 

Single phase

 

Input voltage

Single phase 120VAC, +10% to -40% 2 (72VAC to 132 VAC)

208/240VAC, +10%

 

to -40%1

Input

 

 

 

 

(125 VAC to 229VAC)

Input transformer

 

Isolation Transformer

 

Auto Transformer

 

 

 

 

 

 

 

 

 

Input frequency

 

50/60 Hz +/- 3 Hz 3

 

 

 

 

 

 

 

 

Input capacity 5

1750VA

2250VA

2650VA

2600VA

 

 

 

 

 

 

 

Input power factor

 

Approximately unity (0.95 to 1.0)

 

 

 

 

 

 

 

 

Input voltage

Single phase 120VAC, +10% to -10% 4

Single phase

Bypass

208/240 VAC +/- 10% 4

 

 

 

 

 

Output voltage

 

Single phase 120VAC

 

Single phase

 

 

 

 

 

208/240/120 VAC

 

Overload rating

 

125% for 10 minutes, 150% for 5 minutes

 

 

Output voltage

 

Single phase 120 VAC

 

Single phase

 

 

 

240/208 /120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

Output transformer

 

None

 

Isolation Transformer

 

 

 

 

 

 

Output voltage regulation

 

Within +/- 3%, steady state

 

 

 

 

 

 

 

 

Rated output current (rms)

12.5A

16.6A

20A

9.5A

 

 

 

 

 

 

Output

Maximun output current

31.25Apk

41.5Apk

50Apk

23.75Apk

(peak)

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter overload capacity

 

125% for 60 seconds, 150% for 30 seconds

 

 

Crest factor

 

2.5 at full load

 

 

 

 

 

Output frequency

50/60 Hz (+/- 0.5% in free running mode, line sync range +/-1Hz)

 

Output voltage waveform

Computer-grade sine wave with less than 3.0% total harmonic distortion with linear load

 

 

 

 

 

 

 

Rated load power factor

 

0.7

 

 

 

 

 

 

 

 

 

Effeciency (AC-DC-AC)

80%

80%

80%

79%

 

 

 

 

 

 

Note 1: Currently under development, unit specifications may be changed.

Note 2: Below 79% input voltage unit may begin parallel operation; supplementing input power with battery power. The point at which parallel operation begins is load dependent (for a detailed explanation of Parallel Operation see Appendix C: Parallel Operation).

Note 3: If input frequency is below 50 Hz, the input Voltage must not exceed 103% of rated input Voltage.

Note 4: In BYPASS mode if the Input voltage is below 90% or above 110%, the UPS output will be turned off. (See Appendix D: Bypass Under Voltage/Over Voltage)

Note 5: The input capacity is computed to include peak battery charging power.

38

1800 Series User Manual

Page 38
Image 38
Toshiba 1800 manual Appendix A Specifications