MAINTENANCE | Page 29 |
VACUUM CHECK
A sufficient level of vacuum is necessary for proper performance of the vacuum interrupters. Although vacuum leaks are rare, the vacuum integrity should be checked periodically. The
WARNING
Hazardous voltages are present during dielectric testing which can result in severe injury or death. Only qualified personnel should conduct this testing.
relationship between dielectric breakdown voltage of the contact gap and internal vacuum interrupter pressure has been found to be generally predictable. Therefore, vacuum interrupter integrity is checked by performing a high potential test across the open gap of the interrupter.
TEST EQUIPMENT:
Toshiba offers a compact vacuum checker (Type
PRECAUTIONS:
Applying abnormally high voltage across a pair of contacts in vacuum may produce
TEST PROCEDURE:
1.The circuit breaker should be disconnected from the main circuit and be in the OFF position.
2.Connect all the line side primary terminals together and to the output of the vacuum checker or AC
3.Increase the voltage from zero to 22kV AC at a rate of approximately 2kV per second. Hold the voltage at this value for 1 minute and observe the current drawn by the interrupter.
4.Decrease the voltage back to zero.
Fig. 34 Toshiba Portable Vacuum Checker
WARNING
Radiation exposure hazard.