Page 30 | MAINTENANCE |
CRITERIA:
1.If a current flow above 5 milliamperes is observed or if breakdown occurs, one or more of the interrupters has insufficient vacuum and must be replaced.
Exception: If the current exceeds 5 milliamperes the first time the voltage is brought up, reduce the voltage to zero and increase it again. It may be necessary to repeat this procedure a few times.
2.If the breaker fails to meet criteria 1, then repeat the test on each pole separately to identify the damaged interrupter or interrupters.
3.If the voltage can be held for 1 minute and the current flow does not exceed 5 milliamperes, the interrupter has a sufficient vacuum level.
After the test is complete, discharge any residual static charge from the primary terminals of the circuit breaker.
If a vacuum checker or AC
Fig. 35 Application of Test Voltage for Vacuum Check
22kV AC | 1 minute |
| |
(31kV DC) |
|
Voltage |
|
Zero |
|
15 sec | 15 sec |
| Time |
WARNING
Do not use DC