Page 14 | INSTALLATION |
MOUNTING DIRECTLY TO A SHELF
The shelf should be flat and level within ± 0.5
mm(± 0.02 in.). If there are any noticeable gaps between the breaker and the shelf, fill them in using flat washers as spacers.
Check to make sure the breaker
1.Fasten the breaker onto steel angles or to a flat plate (Fig. 13). Use M8 hex head bolts (either 50 mm or 35 mm). The tightening torque should be
2.Either mounting method shown in (Fig. 14) may be used.
Fig. 13 Mounting Breaker to Flat Plate or Angles
PANEL |
ANGLE |
M8 x 35MM OR M8 x 50MM BOLT |
Fig. 14 Optional Hardware Orientation