MOUNTING DIRECTLY TO A SHELF

Page 14

INSTALLATION

MOUNTING DIRECTLY TO A SHELF

The shelf should be flat and level within ± 0.5

mm(± 0.02 in.). If there are any noticeable gaps between the breaker and the shelf, fill them in using flat washers as spacers.

Check to make sure the breaker On-Off indicator shows OFF (green), then mount it by following the steps below:

1.Fasten the breaker onto steel angles or to a flat plate (Fig. 13). Use M8 hex head bolts (either 50 mm or 35 mm). The tightening torque should be 120-150 kgf-cm (9-11 ft-lb).

2.Either mounting method shown in (Fig. 14) may be used.

Fig. 13 Mounting Breaker to Flat Plate or Angles

PANEL

ANGLE

M8 x 35MM OR M8 x 50MM BOLT

Fig. 14 Optional Hardware Orientation