GENERAL DESCRIPTION

SAFETY DEVICES

Safety interlocks and guards are provided as an integral part of the equipment design. These devices are provided for safety to the operator.

DANGER

Never defeat, modify or bypass any safety devices, interlocks or operating mechanism. This would make the equipment unsafe. Fire, explosion, severe injury, death and property damage could occur.

WARNING

Do not operate this equipment unless all covers and panels are in place.

Fig. 3 Interlock Release Lever

INTERLOCK RELEASE LEVER

The interlock release lever on the front of the circuit breaker (Fig. 3) prevents moving the circuit breaker to or from the CONNECTED position while it is ON (main contacts closed).

If the circuit breaker is ON, the interlock release lever cannot be raised, preventing movement of the breaker in or out of the cell. If the lever is raised when the circuit breaker is OFF, an interlock prevents the circuit breaker from closing until the lever is returned to its lowered position.

DANGER

Hazard of fire, explosion, severe injury, death and property damage.

Never attempt to move a circuit breaker that is ON (main contacts closed) into or out of the CONNECTED position.

Never attempt to forcibly override the interlock release lever.