Toshiba HV6FS-MLD instruction manual Electrical Operation Flow Chart

Models: HV6FS-MLD

1 38
Download 38 pages 2.46 Kb
Page 27
Image 27

OPERATION

Page 23

Circuit Breaker Open

Control Power Applied

Motor Begins Operating

Closing Springs Begin Charging

Closing Springs Charged

Motor Stops

Closing Signal Given

Close Coil Energized

-- - - Spring Status Indicator Changes to Yellow

-- - - Standby for Close Operation

Circuit Breaker Closes

- - - - Spring Status Indicator Changes to White

 

 

and On-Off Status Changes to ON

 

 

 

 

 

Auxiliary Relay Closes

 

 

 

- - - - Next Close Operation is Not Possible

 

 

Anti-Pumping Circuit Completed

 

 

Unless Close Signal is Canceled

 

 

 

 

 

Opening Signal Given

 

 

 

 

 

 

 

Trip Coil Energized

 

 

 

 

Circuit Breaker Opens

- - - - On-Off Status Indicator Changes to OFF

Fig. 30 Electrical Operation Flow Chart

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net