– 18 –
*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

RAV-SM1103AT-E1
Pressure Pipe surface temp. Temp

*

Comp.

*

Comp.
(MPa) (kg/cm
2
G)
Pd Ps Pd Ps TD TS TC TL TE Hz Fan In Out
Cooling
Standard 3.44 0.92 35.1 9.4 82 8 10 56 39 47 HIGH 27/19 35/–
Overload 3.73 1.18 38.1 12.0 82 15 17 59 48 42 HIGH 32/24 43/–
Low load 1.49 0.70 15.2 7.1 39 8 3 23 22 30 LOW 18/15.5 –5/–
Heating
Standard 2.80 0.61 28.6 6.2 80 0 46 7 1 48 HIGH 20/– 7/6
Overload 3.43 1.08 35.0 11.0 82 14 55 12 13 24 LOW 30/– 24/18
Low load 2.20 0.25 22.4 2.6 76 -19 36 -16 -16 55 HIGH 15/–
–10/(70%)
3.52 0.85 35.9 8.7 87 8 9 57 39 54 HIGH 27/19 35/–
3.78 1.12 38.6 11.4 84 15 17 59 47 45 HIGH 32/24 43/–
1.51 0.71 15.4 7.2 40 7 3 23 23 30 LOW 18/15.5 –5/–
2.88 0.60 29.4 6.1 85 147 6161
HIGH 20/– 7/6
3.41 1.08 34.8 11.0 81 14 54 13 13 24 LOW 30/– 24/18
2.35 0.24 24.0 2.4 80 -19 40 -16 -16 73 HIGH 15/–
–10/(70%)