6.Short intermittent operation preventive control

1)For 3 to 10 minutes after operation start, in some cases, the compressor does not stop to protect the compressor even if receiving the thermostat-OFF signal from indoor.

However it is not abnormal status. (The operation continuance differs according to the operation status.)

2)When the operation stops by the remote controller, the operation does not continue.

7.Current release value shift control

1)This control purposes to prevent troubles of the electronic parts such as the compressor driving elements and the compressor during cooling operation.

2)The current release control value (I1) is selected from the following table according to TO sensor value.

Current release control value (I1)

[A]

 

 

 

 

 

 

 

Temperature range

SM110

 

SM140

 

 

 

 

 

 

 

 

47°C TO

15.0

 

15.5

 

 

 

 

 

 

 

 

44°C TO < 47°C

16.8

 

17.4

 

 

 

 

 

 

 

 

39°C TO < 44°C

17.7

 

18.3

 

 

 

 

 

 

 

 

TO error

15.0

 

15.5

 

 

 

 

 

 

 

8.Over-current protective control

1)When the over-current protective circuit detected an abnormal current, stop the compressor.

2)The compressor restarts after 2 minutes 30 seconds setting [1] as an error count.

3)When the error count [8] was found, determine an error and restart operation is not performed.

4)For the error display contents, confirm on the check code list.

9.High-pressure release control

1)The operation frequency is controlled to restrain abnormal rising of high pressure by TL sensor in cooling operation and TC sensor in heating operation.

2)When TL sensor in cooling operation or TC sensor in heating operation detects abnormal temperature of the stop zone, stop the compressor and the error count becomes +1.

3)When the compressor stopped with 2), the operation restarts from the point of the normal operation zone (e point or lower) where it returned after 2 minutes 30 seconds.

4)The error count when the compressor stopped with 2) is cleared after the operation continued for 10 minutes.

If the error count becomes [10] without clearing, the error is determined and reactivation is not performed.

5)For the error display contents, confirm on the check code list.

HEAT TC / COOL TL

[˚C]

HEAT

COOL

TC

TL

a

Abnormal stop

a

62°C

63°C

b

Frequency normal down

b

57°C

62°C

c

Frequency slow down

c

55°C

60°C

d

Frequency hold

Frequency slow up (Up to command)

e

As command is

d

53°C

58°C

 

 

 

e

49°C

54°C

10. Defrost control

cIn heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to D zone.

dThe defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or it also is finished when condition of 7°C < TE < 12°C has continued for 1 minute. The defrost operation is also finished when defrost operation has continued for 10 minutes even if TE sensor temperature has become 7°C or lower.

eAfter defrost operation has finished, the compressor and the outdoor fan start heating operation after stopped for approx. 40 seconds.

– 35 –

Page 35
Image 35
Toshiba RAV-SM1403AT-E1 service manual Current release value shift control, Defrost control, Current release control value

RAV-SM1403AT-E1 specifications

The Toshiba RAV-SM1403AT-E1 is a state-of-the-art air conditioning system designed for residential and commercial applications. Its advanced features and cutting-edge technology ensure optimal cooling and heating performance, making it a popular choice among consumers and businesses alike.

One of the standout characteristics of the RAV-SM1403AT-E1 is its energy efficiency. This model is equipped with a highly efficient inverter compressor that adjusts its output based on the cooling load required, which results in significant energy savings compared to traditional air conditioning systems. Its impressive Seasonal Energy Efficiency Ratio (SEER) ratings highlight its ability to provide effective climate control while minimizing electricity consumption.

The RAV-SM1403AT-E1 utilizes Toshiba’s innovative DC inverter technology, which allows for smoother and quieter operation. This means that users can enjoy a comfortable indoor environment without the disruptive noise often associated with conventional models. In addition to its quiet operation, this air conditioner also features an advanced air filtration system that helps to maintain indoor air quality by removing dust, allergens, and other pollutants.

Another major feature of this system is its versatility in installation. The RAV-SM1403AT-E1 can be installed in various configurations, allowing it to adapt to different spaces and design requirements. It supports multiple indoor units that can be connected to a single outdoor unit, providing flexibility for cooling or heating multiple areas simultaneously.

Smart technology is also integrated into the RAV-SM1403AT-E1. Users can take advantage of remote control options, including Wi-Fi capabilities that allow for convenient management of the air conditioning system via smartphones or tablets. This level of control ensures that users can adjust settings even when they are not present, increasing comfort and efficiency.

The build quality of the Toshiba RAV-SM1403AT-E1 reflects its durability and reliability. Designed to withstand varying environmental conditions, it includes corrosion-resistant features that extend the lifespan of the unit, making it a practical investment for both home and commercial use.

In summary, the Toshiba RAV-SM1403AT-E1 combines energy efficiency, advanced technology, and flexible installation options, making it an excellent choice for those seeking a high-performance air conditioning solution. With its innovative features and commitment to sustainability, this model stands out in the competitive HVAC market.