– 61 –
Resistance (kΩ) (50˚C or lower)
Resistance (kΩ) (50˚C or higher)
0
0
50
100
150
200
0
5
10
15
20
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Resistance (kΩ)
0
0
10
20
30
40
Output voltage (V)
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)

Temperature sensor Temperature – Resistance value characteristic table

TA, TC, TCJ, TE, TS, TO sensors

Representative value

TD, TL sensors

Representative value

TA, TC, TCJ, TE, TS, TO sensors

TD, TL sensors

Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (kΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (kΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.