– 33 –
Objective model
I1 value [A]
SM110 SM140
COOL HEAT COOL HEAT
20.4 21.2 21.2 21.2

3. Current release control

The output frequency and the output voltage are controlled by AC current value detected by T20 on the

outdoor P.C. board so that input current of the inverter does not exceed the specified value.

I1
I1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold

4. Outdoor fan control

Allocations of fan tap revolutions [rpm]

W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE WF
SM110 250 280 320 360 410 460 520 580 640 700 760 880 880 900 930
SM140 250 280 320 360 410 460 520 580 640 700 760 880 880 900 970

4-1. Cooling fan control

1) An outdoor fan is controlled by TL sensor, TO sensor and operation frequency. An outdoor fan is con-

trolled at 1-tap interval of DC fan control.

2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone

in the following table but it is controlled with TL sensor temperature after then.

+

1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Temp. range
SM110
MIN.
38
˚C
TO
29
˚C
TO < 38˚C
15
˚C
TO < 29˚C
5
˚C
TO < 15˚C
0
˚C
TO < 5˚C
– 4
˚C
TO < 0˚C
TO < – 4
˚C
TO error
MAX. MIN. MAX. MIN. MAX.
W6 WB W8
SM110:WD
SM140:WF
WA
SM110:WD
SM140:WF
W5 WA W7 WD W9
SM110:WD
SM140:WF
W3 W7 W5 W9W7 WB
W2 W5 W4 W7 W6 W9
W1 W3 W3 W5 W4 W7
W1 W2 W2 W4 W3 W5
OFF OFF OFF OFF OFF OFF
OFF WB OFF OFF
SM110:WD
SM140:WF
SM110:WD
SM140:WF
Under 30.0 Hz Over 30.0,
under 43.8 Hz Over 43.8 Hz
SM140 Under 34.2 Hz Over 34.2,
under 52.2 Hz Over 52.2 Hz
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
WF tap
TL
55˚C
38˚C
35˚C
58˚C