Roberts Gorden UHD[X][S][R] 200 DUCT HEATER INSTALLATION 5.1 General, Minimum Inlet Duct Length

Models: UHD[X][S][R] 175 UHD[X][S][R] 150 UHD[X][S][R] 200 UHD[X][S][R] 225 UHD[X][S][R] 350 UHD[X][S][R] 400 UHD[X][S][R] 250 UHD[X][S][R] 300

1 50
Download 50 pages 58.83 Kb
Page 13
Image 13
SECTION 5: DUCT HEATER INSTALLATION 5.1 General

SECTION 5: DUCT HEATER INSTALLATION

SECTION 5: DUCT HEATER INSTALLATION 5.1 General

To connect the inlet and outlet ducts to the heater, Duct-Mate or similar flanges may be slid over the duct connector flanges supplied on the unit and secured with screws. The connection to the duct then can be made using the Duct-Mate clips. The ducts must have removable access panels upstream and downstream of the heater. These panels must be of appropriate size and placement so that smoke or reflected light could be observed to indicate the presence of leaks in the heat exchanger. Covers for these openings should be sealed to prevent leakage.

Any transition into the inlet of the heater should be smooth, with a taper of no more than 15°. If elbows are required, they should be of either broad radius or fitted with properly designed air turns. Consult a professional to ensure air turns are properly designed.

The heater must be installed on the positive pressure side of the circulating air blower. Air flow through the heater must be as shown on Page 7, Figure 2 and may not be reversed. The air flow must be adjusted such that it is within the acceptable

5.1.1 Minimum Inlet Duct Length

range shown on Page 7, Section 5.1.2. The minimum inlet duct lengths shown on Page 7, Section 5.1.1 must be observed. Pressure drop through the heat exchanger at various air flows is shown on Page 7, Section 5.1.2.

Figure 2: Air Flow Direction

Model

Duct Length

Duct Size (W X H)

UHD[X][S][R] 150-175

52" (132 cm)

28" x 24" (71 cm x 60 cm)

UHD[X][S][R] 200-250

60" (162 cm)

28" x 32 1/4" (71 cm x 103 cm)

UHD[X][S][R] 300-400

75" (190 cm)

28" x 40 1/2" (71 cm x 82 cm)

5.1.2 Temperature Rise and Pressure Drop Ranges

 

UHD[X][S][R] 150

 

UHD[X][S][R] 175

 

UHD[X][S][R] 200

 

UHD[X][S][R] 225

Airflow

 

Temperature

Pressure

Airflow

 

Temperature

Pressure

Airflow

Temperature

Pressure

Airflow

Temperature

Pressure

(CFM)

 

Rise (°F)

Drop

(CFM)

 

Rise (°F)

Drop

(CFM)

Rise (°F)

Drop

(CFM)

Rise (°F)

Drop

 

(in wc)

 

(in wc)

(in wc)

(in wc)

 

 

 

 

 

 

 

 

 

 

1,360

 

83

0.02

1,400

 

95

0.03

2,050

73

0.025

2,100

80

0.035

1,950

 

58

0.035

2,180

 

62

0.06

2,600

58

0.035

2,800

61

0.052

2,800

 

41

0.057

3,244

 

42

0.10

3,600

42

0.056

4,600

37

0.110

3,700

 

31

0.083

4,370

 

31

0.15

5,500

28

0.100

6,230

27

0.167

4,700

 

24

0.12

5,160

 

27

0.19

6,570

23.5

0.129

7,400

23

0.214

5,800

 

20

0.16

6,850

 

20

0.29

7,750

20

0.163

8,300

20

0.253

 

 

 

 

 

 

 

 

 

UHD[X][S][R] 250

 

UHD[X][S][R] 300

 

UHD[X][S][R] 350

 

UHD[X][S][R] 400

Airflow

 

Temperature

Pressure

Airflow

 

Temperature

Pressure

Airflow

Temperature

Pressure

Airflow

Temperature

Pressure

(CFM)

 

Rise (°F)

Drop

(CFM)

 

Rise (°F)

Drop

(CFM)

Rise (°F)

Drop

(CFM)

Rise (°F)

Drop

 

(in wc)

 

(in wc)

(in wc)

(in wc)

 

 

 

 

 

 

 

 

 

 

2,350

 

80

0.05

2,700

 

23

0.02

3,120

86

0.03

3,420

86

0.04

3,000

 

63

0.07

4,735

 

50

0.06

4,880

56

0.07

5,200

57

0.08

4,400

 

43

0.13

6,813

 

35

0.12

6,612

41

0.123

6,700

45

0.13

5,900

 

32

0.19

8,000

 

30

0.17

9,140

30

0.23

8,850

34

0.21

7,625

 

25

0.28

9,300

 

26

0.22

10,500

26

0.30

11,600

26

0.36

8,850

 

22

0.35

10,200

 

86

0.27

13,600

22

0.48

14,200

22

0.53

7

Page 13
Image 13
Roberts Gorden UHD[X][S][R] 200 DUCT HEATER INSTALLATION 5.1 General, Minimum Inlet Duct Length, Air Flow Direction