Roberts Gorden UHD[X][S][R] 225, UHD[X][S][R] 300, UHD[X][S][R] 250 General Technical Data Table

Models: UHD[X][S][R] 175 UHD[X][S][R] 150 UHD[X][S][R] 200 UHD[X][S][R] 225 UHD[X][S][R] 350 UHD[X][S][R] 400 UHD[X][S][R] 250 UHD[X][S][R] 300

1 50
Download 50 pages 58.83 Kb
Page 44
Image 44
15.2 General Technical Data Table

UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

15.2 General Technical Data Table

 

 

UHD

UHD

UHD

UHD

UHD

UHD

UHD

UHD

 

 

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

 

Model

150

175

200

225

250

300

350

400

 

 

 

 

 

 

 

 

 

 

Full Load Amps @ 115 V

A

2

2

2

2

2

2

6

6

 

 

 

 

 

 

 

 

 

 

Minimum Air Volume

CFM

1360

1400

2050

2100

2350

2700

3120

3420

 

 

 

 

 

 

 

 

 

 

Temperature Rise @

°F

83

95

73

80

80

86

86

86

Minimum Air Volume

(°C)

(28)

(35)

(23)

(27)

(27)

(30)

(30)

(30)

Heat Exchanger Pressure

 

 

 

 

 

 

 

 

 

Drop @ Minimum Air Volume

in wc

0.02

0.03

0.025

0.035

0.05

0.02

0.03

0.04

 

 

 

 

 

 

 

 

 

 

Maximum Air Volume

CFM

5800

6850

7750

8300

8850

10200

13600

14200

 

 

 

 

 

 

 

 

 

 

Temperature Rise @

°F

20

20

20

20

22

23

22

22

Maximum Air Volume

(°C)

(7)

(7)

(7)

(7)

(6)

(5)

(6)

(6)

 

 

 

 

 

 

 

 

 

 

Heat Exchanger Pressure

 

 

 

 

 

 

 

 

 

Drop @Maximum Air Volume

in wc

0.16

0.29

0.163

0.253

0.35

0.27

0.48

0.53

Flue Size*

in

 

 

 

4 - All Models

 

 

 

(cm)

 

 

 

(10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Intake*

in

4

4

4

4

4

5

5

5

(cm)

(10)

(10)

(10)

(10)

(10)

(13)

(13)

(13)

 

 

 

 

 

 

 

 

 

 

 

* Do not exceed the maximum length of flue stated or heater may not operate properly.

15.3 Technical Data Table

 

 

UHD

UHD

UHD

UHD

UHD

UHD

UHD

UHD

 

Model

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]

[X][S][R]]

[X][S][R]

 

 

150

175

200

225

250

300

350

400

Total Input

(Btu/h) x (1000)

150

175

200

225

250

300

350

385

 

 

 

 

 

 

 

 

 

 

Total Output

(Btu/h) x (1000)

123

143.5

164

184.5

205

246

287

315.7

 

 

 

 

 

 

 

 

 

 

Efficiency

%

 

 

 

82 - All Models

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Pressure

in wc

3.2

3.4

3.7

3.7

4.0

2.7

2.7

3.3

 

 

 

 

 

 

 

 

 

 

LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Pressure

in wc

9.9

10.4

10.5

10.7

10.5

9.4

9.3

11.1

 

 

 

 

 

 

 

 

 

 

38

Page 44