UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 13: TROUBLESHOOTING
13.1General
START
Are gas & electrical | No | Turn on supplies. | |
supplies on? | |||
|
|
Yes |
|
|
| |
Is ignition control showing a |
| Wait 10 - 15 minutes for |
| |
YesYes | limit switch to cool. Does | Yes | ||
"4 flashes" LED code? | ||||
|
| fan stop running? |
| |
|
| No |
| |
|
| Replace temperature limit |
| |
|
| switch. |
| |
No |
|
|
| |
Is ignition control showing a | Yes | Burner has locked out due |
| |
to ignition failure. Use |
| |||
"2 flashes" LED code? |
| Troubleshooting for Automatic |
| |
|
|
| ||
|
| Ignition Burner Systems |
| |
|
| section to test burner. |
| |
No |
|
|
| |
Does the flue blower run? | No | Use Troubleshooting for |
| |
Flue Blower section to test |
| |||
|
| |||
|
| fan. |
| |
Yess |
|
|
|
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
Fan and limit switch are operating normally.
With external controls (i.e. |
| Has burner “Locked Out”? No | |
thermostat) on, does the No | |||
burner continue through the |
|
| |
heating cycle? |
|
| |
|
| Yes | |
|
| Use Troubleshooting for | |
|
| Automatic Ignition Burner | |
|
| Systems section to test burner. | |
Yes |
|
| |
Heater Operating |
| If problems persist, contact | |
No | |||
TROUBLESHOOT ENDS. | |||
|
The limit switch has tripped. See Manual Reset No
Limit Switch Figure.
Yes
Ensure air flow through
heat exchanger is
appropriate per the rating
plate.
28