Roberts Gorden UHD[X][S][R] 225 Automatic Burner Control Sequence, Gas Valve, End View, Top View

Models: UHD[X][S][R] 175 UHD[X][S][R] 150 UHD[X][S][R] 200 UHD[X][S][R] 225 UHD[X][S][R] 350 UHD[X][S][R] 400 UHD[X][S][R] 250 UHD[X][S][R] 300

1 50
Download 50 pages 58.83 Kb
Page 28
Image 28
Figure 11: Automatic Burner Control Sequence

UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

Figure 11: Automatic Burner Control Sequence

Burner Sequence for Ignition Control

START

Thermostat 24 V

RUN

SHUT DOWN

Flue Blower

Pressure

 

Switch

C

 

Ignition Spark

Start Gas Valve

Flame Signal

P

30 Seconds Purge*

30 Seconds Post Purge

NO

 

NC

ts = 10 Seconds

 

*Purge time begins at pressure switch change over.

Required Incoming Signals

If at any stage the flame fails, the control will retry

Signals Output By Control

Figure 12: Gas Valve

for ignition. The control has four trials for ignition before a one hour lockout.

END VIEW

TOP VIEW

 

 

Regulator

 

 

½PSI

 

 

C

 

 

IN

 

 

 

ON

Gas Inlet

OFF

Outlet

 

 

Pressure

 

 

 

Description

Part Number

 

Gas Valve 150 - 225 NG

90032505

 

Gas Valve 150 - 225 LP

90032506

 

Gas Valve 250 - 400 NG

90032520

Inlet Pressure

Gas Valve 250 - 400 LP

90032521

 

 

22

 

 

Page 28
Image 28
Roberts Gorden UHD[X][S][R] 225, UHD[X][S][R] 300 Automatic Burner Control Sequence, Gas Valve, End View, Top View