14.6 Pressure Switch

UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

14.6 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting. Carry out a start-up after working on or changing a pressure switch. See Page 21, Section 10.

 

UHD[X][S][R]

UHD[X][S][R]

UHD[X][S][R]

UHD[X][S][R]

UHD[X][S][R]

MODEL

150 - 175

200 - 225

250

300 - 350

400

 

 

 

 

 

 

Pressure Switch

 

 

 

 

 

Kit P/N

90439802

90439808

90439803

90439807

90439808

 

 

 

 

 

 

Color Code

yellow

orange

gray

brown

orange

 

 

 

 

 

 

Set Point (in wc)

.32

.79

.41

.68

.79

 

 

 

 

 

 

Pressure Switch

 

 

 

 

 

Snap Ring P/N

90439850

90439850

90439850

90439850

90439850

 

 

 

 

 

 

14.7 Ignition Control

The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable and all other wiring.

14.8 Limit Switches

14.8.1 Removal and Replacement

1.Remove the electrical connections to the switch.

2.Unscrew the two screws securing the switch.

3.Fit a new switch with two screws.

4.Reconnect the electrical connections and test operation.