Toshiba VF-AS1, VF-PS1 instruction manual Title, E 6 5 8 1 3 6

Models: VF-AS1 VF-PS1

1 10
Download 10 pages 12.86 Kb
Page 4
Image 4
Title

E 6 5 8 1 3 6 4

1.1.1.Switching circuit connection diagram, Time chart, Parameter settings

F L

Inverter

protective

 

Inverter

 

 

action signal

 

trip occurs

Speed detection time

 

 

FLA

FLC

FLX

Setting

 

 

 

 

 

 

 

Frequency after speed is

 

 

 

 

frequency

 

 

 

 

 

 

 

detected

 

 

ON

OFF

 

0Hz

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

Inverter-side switching wait

 

 

 

 

 

 

 

 

 

 

P24-OUT1(RY1)

 

time *2

 

 

 

 

 

for inverter run

ON

 

 

ON

X

 

 

output

 

 

 

 

 

Commercial power

 

 

 

 

 

 

 

 

RY1

 

 

P24-OUT2(RY2)

 

switching wait time



 

 

 

 

 

 

 

(Inverter)

 

MC2

for commercial

 

ON

 

 

 

 

power run output

 

 

 

 

 

 

 

 

 

 

 

 

Run signal

ON

 

 

ON

MC2

 

 

F-CC

 

 

 

MC3

 

 

 

 

 

 

 

Stand-by signal

 

 

 

 

RY2

 

 

 

 

 

 

 

 

ST-CC

ON

 

 

 

(Commercial

 

 

 

 

 

X

 

 

 

 

 

 

power)

MC1

 

 

 

 

 

 

 

Reset signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RES-CC

 

 

 

 

MC3

X

 

 

Inverter run

Commercial power run

Inverter run

 

 

F

 

 

 

 

 

Title

Function

Adjustment range

Setting value

 



Output signal selection of commercial

0 to 3

1 (Automatic switching in case

power/inverter switching

of trip)

 

 

 

 

*3

Inverter side switching waiting time

0.1 to 10.0 seconds

Different for each model

*3

Commercial power side switching waiting

0.37 to 10.0 seconds

0.62

 

time

 

 

*1

Input terminal selection #6 (S2)

0 to 135

20

 

 

 

(Emergency stop)

 

 

 

46



Output terminal selection #1 (OUT1)

0 to 119

(Commercial power/inverter

 

 

 

switching output 1)

 

 

 

48



Output terminal selection #2 (OUT2)

0 to 119

(Commercial power/inverter

 

 

 

switching output 2)

*1:Be careful about Items 5 and 7 in 1.3, “Precautions.”

*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of  *3: and  are included the operation time of the relay and the magnet contactor.

In almost all cases, it is not necessary to change these parameter settings.

3

Page 4
Image 4
Toshiba VF-AS1, VF-PS1 instruction manual Title, E 6 5 8 1 3 6