Physical | 50 Hz Compressors |
Dimensions | (English Units) |
|
|
|
|
|
|
|
|
|
|
|
| ENGLISH UNITS |
|
|
|
| ||
|
|
|
|
|
| Envelope |
| Clearance |
| Unit Dimensions |
| |||
|
|
|
|
|
| W/O Unit | With Unit |
|
|
|
|
| W/O Unit | With Unit |
|
|
| Shell |
|
| Mounted | Mounted | Tube |
|
|
|
| Mounted | Mounted |
|
| Shell | Arrange- |
|
| Starters | Starters | Pull |
|
|
|
| Starters | Starters |
| COMP | Size | ment |
| EL | EW | EW | CL1 | CL2 | Length | Height | Width | Width | |
| 320 | SS |
| 26' 5” | 10' 6 1/4” | 11' 4 1/2” | 11' 9” | 3' 5” | 11' 3” | 7' 9 3/4” | 5’ 9 1/4” | 6' 7 1/2” | ||
| 320 | SL & LL | 33' 11 1/4” | 10' 6 1/4” | 11' 4 1/2” | 15' 6” | 3' 5” | 15' 0 1/4” | 7' 9 3/4” | 5” 9 1/4” | 6' 7 1/2” | |||
| 500 | SS | 26' 6 3/8” | 11' 4 5/8” | 12' 6 7/8” | 11' 9” | 3' 6 3/8” | 11' 3” | 8' 2 1/4” | 6' 7 5/8” | 7' 9 7/8” | |||
C | 500 | SL & LL | 34' 0 5/8” | 11' 4 5/8” | 12' 6 7/8” | 15' 6” | 3' 6 3/8” | 15' 0 1/4” | 8' 2 1/4” | 6' 7 5/8” | 7' 9 7/8” | |||
V | 500 | SS | 26' 6 3/8” | 11' 4 5/8” | 12' 5 1/2” | 11' 9” | 3' 6 3/8” | 11' 3” | 8' 2 1/2” | 6' 7 5/8” | 7' 8 1/2” | |||
H | 500 | SL & LL | 34' 0 5/8” | 11' 4 5/8” | 12' 5 1/2” | 15' 6” | 3' 6 3/8” | 15' 0 1/4” | 8' 2 1/2” | 6' 7 5/8” | 7' 8 1/2” | |||
E | 800 | SS | 27' 4 1/4” | 12' 5 1/4” | 13' 4 5/8” | 11' 9” | 4' 4 1/4” | 11' 3” | 9' 6 3/8” | 7' 11 1/4” | 8' 7 5/8” | |||
| 800 | SL & LL | 34' 10 1/2” | 12' 5 1/4” | 13' 4 5/8” | 15' 6” | 4' 4 1/4” | 15' 0 1/4” | 9' 6 3/8” | 7' 11 1/4” | 8' 7 5/8” | |||
| 500 | SS | 26' 6 3/8” | 11' 4 5/8” | 12' 5 3/4” | 11' 9” | 3' 6 3/8” | 11' 3” | 8' 7 1/4” | 6' 7 5/8” | 7' 8 3/4” | |||
| 500 | SL & LL | 34' 0 5/8” | 11' 4 5/8” | 12' 5 3/4” | 15' 6” | 3' 6 3/8” | 15' 0 1/4” | 8' 7 1/4” | 6' 7 5/8” | 7' 8 3/4” | |||
| 800 | SS | 27' 4 1/4” | 12' 5 1/4” | 13' 4 5/8” | 11' 9” | 4' 4 1/4” | 11' 3” | 9' 8” | 7' 11 1/4” | 8' 7 5/8” | |||
C | 800 | SL & LL | 34' 10 1/2” | 12' 5 1/4” | 13' 4 5/8” | 15' 6” | 4 4 1/4” | 15' 0 1/4” | 9' 8” | 7' 11 1/4” | 8' 7 5/8” | |||
V | 800 | SS | 27' 4 1/4” | 12' 10” | 13' 10 3/4” | 11' 9” | 4' 4 1/4” | 11' 3” | 9' 6 3/4” | 8' 4” | 9' 1 3/4” | |||
H | 800 | SL & LL | 34' 10 1/2” | 12' 10” | 13' 10 3/4” | 15' 6” | 4' 4 1/4” | 15' 0 1/4” | 9' 6 3/4” | 8' 4” | 9' 1 3/4” | |||
G | 1420 | ML & LL | 35' 5 1/4” | 14' 5 3/4” | 15' 0 7/8” | 15' 6” | 4' 11” | 15' 0 1/4” | 10' 1 1/8” | 9' 11 3/4” | 10' 3 7/8” | |||
| 1420 | ML & LL | 35' 5 1/4” | 14' 5 3/4” | 15' 0 7/8” | 15' 6” | 4' 11” | 15' 0 1/4” | 10' 1 1/8” | 9' 11 3/4” | 10' 3 7/8” | |||
| 2100 | LL | 35' 5 1/4” | 15 3 3/4” | 15' 7” | 15' 6” | 4' 11” | 15' 0 1/4” | 11' 0 7/8” | 10' 9 3/4” | 10' 10” | |||
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR TUBE PULL CLEARANCE. |
|
|
|
|
|
| ||||||||
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE. |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| CENTRAVAC WATER CONNECTION PIPE SIZE |
|
|
|
|
|
|
| ||||
| Water |
|
|
|
| Shell Size |
|
|
|
|
|
|
| |
| Passes |
| 032 |
|
| 050 | 080 | 142 | 210 |
|
|
|
|
|
| EVAPORATOR |
|
|
| Nominal Pipe Size (Inches) |
|
|
|
|
|
|
| ||
| 1 PASS |
| 8 |
|
| 10 | 12 | 16 | 16 |
|
|
|
|
|
| 2 PASS |
| 6 |
|
| 8 | 10 | 12 | 14 |
|
|
|
|
|
| 3 PASS |
| 5 |
|
| 6 | 8 | 10 | 12 |
|
|
|
|
|
| CONDENSER 2 PASS | 6 |
|
| 8 | 10 | 12 | 14 |
|
|
|
|
|
41 |