Trane RT-PRC007-EN manual Performance Data, Table PD-16-Power Exhaust Fan Performance

Models: RT-PRC007-EN

1 46
Download 46 pages 21.3 Kb
Page 27
Image 27
Table PD-16— Power Exhaust Fan Performance

Performance

Data

Table PD-16— Power Exhaust Fan Performance

Exhaust

External Static Pressure — Inches of Water

Airflow

High Speed

Med Speed

Low Speed

(Cfm)

ESP

ESP

ESP

 

 

 

 

3500

0.900

4000

0.860

4500

0.820

5000

0.780

0.400

5500

0.745

0.380

6000

0.700

0.360

6500

0.660

0.330

7000

0.610

0.400

0.300

7500

0.560

0.365

0.260

8000

0.505

0.330

0.215

8500

0.445

0.300

0.170

9000

0.385

0.255

0.120

9500

0.320

0.210

0.070

10000

0.255

0.165

0.020

10500

0.190

0.125

11000

0.125

0.060

11500

0.065

0.000

12000

0.005

Notes:

1.Performance in table is with both motors operating.

2.High speed = both motors on high speed. Medium speed is one motor on high speed and one on low speed. Low speed is both motors on low speed.

3.Power Exhaust option is not to be applied on systems that have more return air static pressure drop than the maximum shown in the table for each motor speed tap.

RT-PRC007-EN