Mechanical Specifications
Accessories
Roof Curb
The roof curb shall be designed to mate with the unit and provide support and a water tight installation when installed properly.The roof curb design shall allow
Trane Communication Interface (TCI)
Shall be provided to interface with the Trane Integrated Comfort™ System and shall be available factory installed.The TCI shall allow control and monitoring of the rooftop unit via a
The following alarm and diagnostic information shall be available:
UCP Originated Data
•Unit operating mode
•Unit failure status Cooling failure Heating failure
Emergency service stop indication Supply fan proving
Timed override activation
High temperature thermostat status
•Zone temperature
•Supply air temperature
•Cooling status (all stages)
•Stage activated or not
•Stage locked out by UCP
•HPC status for that stage
•Compressor disable inputs
•Heating status
•Number of stages activated
•High temperature limit status
•Economizer status
•Enthalpy favorability status
•Requested minimum position
•Damper position
•Dry bulb/enthalpy input status
•Outside air temperature
•Outside relative humidity
•Sensor Failure Humidity sensor OAT sensor SAT sensor RAT sensor
Zone temperature sensor Mode input Cooling/heating setpoints from sensors
Static pressure transducer Unit mounted potentiometer SAT from potentiometer
Air reset setpoint from potentiometer
•Unit Configuration data Gas or electric heat Economizer present
•High temp input status
•Local setpoint
•Local mode setting
•Inlet Guide Vane position
Tracer Originated Data
•Command operating mode
•Host controllable functions: Supply fan
Economizer
Cooling stages enabled Heating stages enabled Emergency shutdown
•Minimum damper position
•Heating setpoint
•Cooling setpoint
•Supply air tempering enable/disable
•Slave mode (CV only)
•Tracer/Local operation
•SAT setpoint
•Reset setpoint
•Reset amount
•MWU setpoint
•MWU enable/disable
•SAT Reset type select
•Static pressure setpoint
•Static pressure deadband
•Daytime
•Power exhaust setpoint
Zone Sensors
Shall be provided to interface with the Micro unit controls and shall be available in either manual, automatic programmable with night setback, with system malfunction lights or remote sensor options.
ConventionalThermostat Interface (CTI)
This field installed circuit board shall provide interface with electromechanical thermostats or automation systems. Not available with VAV system control.
Differential Pressure Switches
This field installed option allows dirty filter indication. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.
Remote Potentiometer
A remote potentiometer shall be available to remotely adjust the unit economizer minimum position.
HighTemperatureThermostats
Field installed, manually resettable high temperature thermostats shall provide input to the unit controls to shut down the system if the temperature sensed at the return is 135 F or at the discharge 240 F.
Reference Enthalpy Kit
Field installed enthalpy kit shall provide inputs for economizer control based upon comparison of the outside air stream to a definable enthalpy reference point. May also be factory installed.
Comparative Enthalpy Kit
Field installed enthalpy kit shall provide inputs for economizer control based upon comparison of the enthalpies of the return and outdoor air streams. Also available factory installed.
43 |