Trane RT-PRC007-EN manual Electrical Data, Electrical Service Sizing

Models: RT-PRC007-EN

1 46
Download 46 pages 21.3 Kb
Page 32
Image 32
Electrical Data

Electrical Data

Electrical Service Sizing

To correctly size electrical service wiring for your unit, find the appropriate calculations listed below. Each type of unit has its own set of calculations for MCA (Minimum Circuit Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size). Read the load definitions that follow and then find the appropriate set of calculations based on your unit type.

Set 1 is for cooling only and cooling with gas heat units, and set 2 is for cooling with electric heat units.

Load Definitions: (To determine load values, see the Electrical Service Sizing DataTables.)

LOAD1 = CURRENT OFTHE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR)

LOAD2 = SUM OFTHE CURRENTS OF ALL REMAINING MOTORS

LOAD3 = CURRENT OF ELECTRIC HEATERS

LOAD4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE

Set 1. Cooling Only Rooftop Units and Cooling with Gas Heat Rooftop Units

MCA = (1.25 x LOAD1) + LOAD2 + LOAD4

MOP = (2.25 x LOAD1) + LOAD2 + LOAD4

DSS = 1.15 x (LOAD1 + LOAD2 + LOAD4)

Select a disconnect switch size equal to or larger than the DSS value calculated.

Set 2. Rooftop units with Electric Heat

To arrive at the correct MCA, MOP, and RDE values for these units, you must perform two sets of calculations. First calculate the MCA, MOP, and RDE values as if the unit was in cooling mode (use the equations given in Set 1).Then calculate the MCA, MOP, and RDE values as if the unit were in the heating mode as follows.

(Keep in mind when determining LOADS that the compressors and condenser fans don’t run while the unit is in the heating mode).

For units using heaters less than 50 kw.

MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + (1.25 x LOAD3)

For units using heaters equal to or greater than 50 kw.

MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + LOAD3

The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode MCA value calculated above.

MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

The selection MOP value will be the larger of the cooling mode MOP value or the heating mode MOP value calculated above.

Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. NOTE: If selected MOP is less than the MCA, then reselect the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the reselected fuse size does not exceed 800 amps.

RDE = (1.5 x LOAD1) + LOAD2 + LOAD3 + LOAD4

The selection RDE value will be the larger of the cooling mode RDE value or the heating mode RDE value calculated above.

Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. NOTE: If the selected RDE is greater than the selected MOP value, then reselect the RDE value to equal the MOP value.

DSS = 1.15 x (LOAD1 + LOAD2 + LOAD3 + LOAD4)

NOTE: Keep in mind when determining LOADS that the compressors and condenser fans don’t run while the unit is in the heating mode.

The selection DSS value will be the larger of the cooling mode DSS or the heating mode DSS calculated above.

Select a disconnect switch size equal to or larger than the DSS value calculated.

Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. NOTE: If selected MOP is less than the MCA, then reselect the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the reselected fuse size does not exceed 800 amps.

RDE = (1.5 x LOAD1) + LOAD2 + LOAD4

Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. NOTE: If the selected RDE is greater than the selected MOP value, then reselect the RDE value to equal the MOP value.

Table ED-1 —Ton Electrical Service Sizing Data — Electric Heat Module (Electric Heat Only)

Models:TED/TEH 330 thru 600

Electric Heat FLA

Nominal

Nominal

 

 

 

 

 

Unit Size

Unit

 

 

KW Heater

 

 

(Tons)

Voltage

36

54

72

90

108

 

 

FLA

FLA

FLA

FLA

FLA

27½

208

74.9

112.4

30.0

230

86.6

129.9

35.0

460

43.3

65.0

86.6

108.3

 

575

52.0

69.3

86.6

40.0

208

112.4

50.0

230

129.9

 

460

65.0

86.6

108.3

129.9

 

575

52.0

69.3

86.6

103.9

Notes:

1. All FLA in this table are based on heater operating at 208, 240, 480, and 600 volts.

32

RT-PRC007-EN

Page 32
Image 32
Trane RT-PRC007-EN manual Electrical Data, Electrical Service Sizing, Set 2. Rooftop units with Electric Heat