Mechanical Specifications
General
The units shall be dedicated downflow or horizontal airflow.The operating range shall be between 115 F and 0 F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. All components shall be mounted in a weather resistant steel cabinet with a painted exterior.Where top cover seams exist, they shall be double hemmed and gasket sealed to prevent water leakage. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have handles and shall be removable while providing a water and air tight seal. Control box access shall be hinged.The indoor air section shall be completely insulated with fire resistant, permanent, odorless glass fiber material.The base of the unit shall have provisions for crane lifting.
Filters
Two inch, throwaway filters shall be standard on all size units.Two inch “high efficiency”, and four inch “high efficiency” filters shall be optional.
Compressors
Trane
chamber which leads to increased efficiency. Exhaustive testing on the
Refrigerant Circuits
Each refrigerant circuit shall have independent thermostatic expansion devices, service pressure ports and refrigerant line filter driers factory- installed as standard. An area shall be provided for replacement suction line driers.
Evaporator and Condenser Coils
Condenser coils shall have 3/8” copper tubes mechanically bonded to lanced aluminum plate fins. Evaporator coils shall be 1/2” internally finned copper tubes mechanically bonded to high performance aluminum plate fins. All coils shall be leak tested at the factory to ensure pressure integrity. All coils shall be leak tested to 200 psig and pressure tested to 450 psig. All dual circuit evaporator coils shall be of intermingled configuration. Sloped condensate drain pans are standard.
Outdoor Fans
The outdoor fan shall be
Indoor Fan
Units shall have belt driven, FC, centrifugal fans with fixed motor sheaves. All motors shall be circuit breaker protected. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Electric Heaters
Electric heat shall be available for factory installation within basic unit. Electric heater elements shall be constructed of
Gas Heating Section
The heating section shall have a drum and tube heat exchanger(s) design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger(s) 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and also comply with California requirements for low NOx emissions. All units shall have two stage heating.
Controls
Unit shall be completely factory wired with necessary controls and terminal block for power wiring. Units shall provide an external location for mounting fused disconnect device. Microprocessor controls shall be provided for all 24 volt control functions. The resident control algorithms shall
41 |