Trane RT-SVX19A-E4 Clogged filter detector, Smoke detector, High temperature safety thermostat

Models: RT-SVX19A-E4

1 64
Download 64 pages 41.1 Kb
Page 38
Image 38

Controls

Clogged filter detector

This device is mounted in the filter section. The sensor measures the difference in pressure before and after the filter section. The information is sent to the THP03 thermostat, to a Tracker™ or to a BMS.

Smoke detector

This device is used to detect smoke in the air stream. It includes a factory mounted detector connected to a central panel, both fitted in the fan section.

When smoke is detected, it shuts off the unit. A dry contact is available on the control panel for a remote default.

High temperature safety thermostat

This additional safety device is a manual reset thermostat for gas fired units (YKD/YKH), required mainly by the French ERP regulation. It is located in the gas burner section. It stops the gas burner and the supply air fan when the supply air temperature rises to 120°C.

Remote fault relay

This is a factory mounted relay used to send alarm signals (dry contact) to a local BMS or a local control panel. With this relay, the compressor, heating, fan and power supply alarm output signals from the controller are reported to a single dry contact.

Thermostats

6 thermostats are available:

THS01/THP01, THS02/THP02 and THS03/THP03.

"THS" are non programmable thermostats, "THP" are programmable.

01 and 02 series are conventional thermostat, 03 series are dedicated to the controller.

Table 32 - Thermostats features

 

THS01

THP01

THS02

THP02

THS03

THP03

non-programmable

X

-

X

-

X

-

 

 

 

 

 

 

 

programmable

-

X

-

X

-

X

 

 

 

 

 

 

 

electronic

X

X

X

X

X

X

 

 

 

 

 

 

 

unit control type design

electromech.

electromech.

electromech.

electromech.

Reliatel

Reliatel

 

 

 

 

 

 

 

interface card needed

CTI*

CTI*

CTI*

CTI*

none

none

 

 

 

 

 

 

 

for Cooling Only units

X

X

-

-

X

X

 

 

 

 

 

 

 

for Heat Pump units

-

-

X

X

X

X

 

 

 

 

 

 

 

for Gas Fired units

X

X

-

-

X

X

 

 

 

 

 

 

 

Cooling stages

2

2

2

2

2

2

 

 

 

 

 

 

 

auxiliary heating stages

2

2

1

1

2

2

(elec. heater, HWC )

 

 

 

 

 

 

 

 

 

 

 

 

 

heating stages

none

none

1

1

1

1

(heat pump mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid crystal display

X

X

X

X

-

X

*some important features are lost while using the CTI card. Note: thermostats are powered up by the rooftop control (24V)